Loading...
HomeMy WebLinkAboutHallenbeck Pavilion Fire Inspection Certificate 2025-2026 14 W 0 r0 O 14 IZ-1 02 E) u wz � � az z WO zw ao oS � Aw o ao z o x w � U W � aa � FH > o [J�" ►-� W Q O Z ao ° � �' � A NAB �"� x �+ ►'�"� w z A v ca pz- A O W w x w O x �. M O w 0 cn 14 � ;4 v� CA W C!� O w0 � � � Ow A o � Z Fuwa � az � U x W ►� O w �. M ¢ Lo V W ~ O w Zj �j A °� awA >• zo c a O ►-� V A FzowAF w w AG �1 VJ wW �' z � w � w w cn " v W Q U Z U ~ x a w w F d w w w U (� a.4 w FF z o C7 O 00 � z � AzzH cn a f F ¢ w F 00 u< o � w Q M w u, cnV z A 0 a O F A p w E z V � U Fz � A � H � A w z BUILDING DEPARTMENT VILLAGE OF RYE,BROOK Initial Inspection Date: V Pass STEVEN E.FEWS 938 KING STREET,RYE BROOK,NEw YORK 10573 / �2 2S I_J fail BUILDING&FIRE INSPECTOR (914)939-0668 • www.rYebrookmeov Re-Inspection Date: ❑ Pass slcws(alacbrooknv.gov CI fail FIRE. INSPECTION lb Pi,o 'I', NO'I'ICF, OF VIOLATION & ORDER TO REMEDY SAME Site Address: l 19 La k l&-as 314ACA Zone: SBL: 1.3 O. 7 7— l — 4! Occupancy: Cerg.6r4State Use Classification: Business Owner: of Phone: q1 Y— 17.37— J f 00 Building Owner: Phone: /� p �/ Emergency Contact: A u C�`�+ b _ Phone: 'f y� O T IOU Building Representative in Attendance: Take notice that the following violations of the New York State Uniform Fire reve ion&Building Code and/or the Code of the Village of Rye Brook were fo nd to exist at, U (a �� AA ,in the Village of Rye Brook,NY on, See? .5.4"L L2, 20 T person or entity served with this Order to Remedy shall immediately commence to correct all listed violations and shall completely cure each violation described herein by no later than which is thirty(30)days after the date of this Order to Remedy.Furthermore, upon curing any listed violation(s),you shall immediately contact the Building Department during normal business hours to schedule a re-inspection of the premises to confirm full compliance with all applicable codes,laws,rules&regulations. BE ADVISED TIIAT POUR FAILIIRE TO CORRI:CI'ALL VIOLATIONS IS A(RIME I'(INISI IA BLE,111'FINE,IMPRISONMENT OR 110TI1. ------------------------------------------------------------------------------------------------------------------------------------------------------ NcI 1"1•ti N/A 1.PORTABLE FIRE ExTINGUISIIERS (PFE's) a.906.1. Are PFE's installed throughout the space&on the premises as required by code. a. b.906.3.1.Is the maximum travel distance to a PFE 75 feet or less. b._ ✓ c.906.5.Are PFE's conspicuously located&readily accessible. C._ d.906.6.Are PFE's unobstructed/unobscured from view. d._ _✓ _ e.906.7.Are PFE's properly mounted as per the manufacturers instructions. e. f.906.9.Are PFE's properly installed:<40 lbs.max.5'above floor;>40 lbs.max.3.5'above floor. f. 2.FIRE ALARM SYSTEM&SMOKE DETECPORS a.901.6.1. Is the fire alarm system inspected,tested&maintained in accordance with NFPA 72. a. _✓ _ b.907.4.2.1.Are manual pull stations located within 5 feet of exits&within 200 feet of each other. b. c.907.4.2.2. Is the height of the pull station handle located between 42&48 inches above the floor. C._ s� d.907.3. Is a fire alarm system provided in existing buildings as per section 907.3.1 &907.3.2. d. ✓ 3.FIRE SUPPRESSION SPRINKLER SYSTEM&FIRE HYDRANTS a.901.6.1.Is the sprinkler system inspected,tested&maintained in accordance with NFPA 25-13. a._ b.901.6.1.Are the plain valves secured against tampering in the open position. b. A c.901.6.1.Are sufficient clearances maintained from fire sprinkler heads to fixtures or materials. C. d.901.6.1.Is a supply of six spare heads&a wrench maintained on the premises. d._ e.901.6.1.Are sprinkler heads&cover plates unfinished or of factory applied finish only. C._ f.901.6.3.Are records of all system inspections,tests&maintenance reports maintained on the premises. f g.913.5.Is the fire pump inspected,tested&maintained in accordance with this section&NFPA 25. g. h.507.5.2.Is the fire hydrant system properly maintained,operational,compatible w/NST&tested annually. h. ✓ i.507.5.4.Are fire hydrants&fire protection equipment unobstructed. i. j.507.5.5.Is a clear space of not less that 3 feet maintained around all hydrants. j. ✓ k.901.8.Are all fire protection systems in place and maintained untampered. k. INSPECTOR: ILDATE: -1- NO YES N/A 4.STANDPIPE,CABINETS&FIRE DEPARTMENT CONNECTIONS a.901.6.1.Is the standpipe system inspected,tested&maintained in accordance with NFPA 25-14. a. _✓ _ b.901.6.1.Has the required flow test been performed within the past 5 years as per NFPA 25-14. b. _ -L./ c.912.2.3 Are standpipe FDC threads compatible with fire department standards. C. _ top _ d.905.7.Are cabinets containing fire fighting equipment unobstructed/unobscured. d. _ _✓ _ e.905.7.1.Are cabinets containing fire fighting equipment properly identified&labeled. e. _ ✓ _ f.912.2.1.Are exterior FDC's fully visible&recognizable from the point of fire department access. f. _ �✓/ g.912.4.Are all FDC's unobstructed and available for immediate access by the fire department. g. _ _✓ 5.EXITS,MEANS OF EGRESS&OCCUPANCY a. 1031.2.Are exits&exit enclosures continuously maintained free from obstructions or impediments. a. _ Vol _ b. 1031.3.Is the means of egress free from obstructions including accumulated ice&snow. b. JZ c. 1031.6.Are exits maintained unobstructed by furnishings,decorations,draperies,mirrors,etc... C. _ AZ _ d. 1031.7.Are existing emergency escape&rescue openings maintained as per this section. d. e. 1010.1.Are egress doors provided and maintained as required by this section. e. _✓ _ f. 1004.9.Are all spaces having an assembly occupancy posted with an approved occupant load sign. f. ✓ _ g. 1013.1.Are exits marked by a properly located,approved&readily visible exit sign. g. h. 1013.1.Is the maximum travel distance to any exit sign in an exit access corridor 100 feet or less. h. i. 1013.4.Are tactile exit signs complying with ICC/ANSI 117.1.provided as required by code. i. J. 1013.3.Are all exit signs illuminated at all times. j. _✓ _ k.1008.1.Are the means of egress&exit discharge illuminated at all times the building is occupied. k. _ ✓ _ 1. 1018.3.Are public aisles in group B&M occupancies maintained at least 36"wide where fixtures are placed on one side of the aisle&at 44"wide where fixtures are placed on both sides. / in. 1018.3.Are non-public/non-accessible aisles serving less than 50 people maintained at least M. _ ✓ _ 28"wide,or at least 36"wide where serving 50 or more people. 6.COMBUSTIBLE STORAGE&WASTE MATERIALS a.304.1.Is the building(s)and premises maintained free from accumulated combustible waste material. a. _ ✓ _ b.304.1.2.Is property free from weeds,grass,vines or other growth capable of being ignited. b. c.304.2.Is combustible rubbish stored so as not to create a nuisance or hazard to the public. C. _ _✓ _ d.315.3.Are combustible materials properly stored&separated from ignition sources. d. _ _✓ _ e.315.3.1. Is storage maintained 24"or more below the ceiling in nonsprinklered buildings, e. _ _✓ _ and 18"or more below sprinkler head deflectors in sprinklered buildings. f.315.3.2.Are exits&exit enclosures maintained free from stored combustible materials. f. _ _✓ _ g.315.3.3.Are boiler,mechanical&electrical rooms maintained free from stored combustible material. g. _ _✓ _ h.313.1.Is building maintained free from stored fueled equipment.(motorcycles,mopeds,mowers,etc...) h. _ ✓ 7.ELECTRICAL a.604.1.Is the building free from modified/damaged wiring,devices,appliances,equipment a._ ✓ and maintained free from electrical hazards. b.604.2.Are electrical service equipment areas properly illuminated. b._ _✓ _ c.604.3.Are proper working space clearances provided&maintained for electrical service equipment. C._ ✓ _ d.604.3.Are electrical service equipment working spaces free from any stored materials. d._ _✓ _ e.604.3.1.Are all electrical control panel room doors,panel boards&disconnects properly labeled. e._ _✓ _ f.604.4. Is the building free from unfused multi-plug electrical adapters. f g.604.5.Are electrical extension cords being used in a safe manner as per code. g. h.604.6.Are all junction,switch&outlet boxes fitted with approved covers or plates. h. i.604.6.Is the building free from open-wiring spliced electrical connections. i. </ j.604.8.Are electrical motors maintained free from accumulated oil,dirt&debris. j. k.915.1.Are Carbon Monoxide Detectors installed&maintained as required by this section and by 1103.9. k._ INSPECTOR: DATE: -2- Revised 6/1/2024 No VE's N/A 8.ELEVATORS.DUMawArl'ERS&ESCALATORS a.[PM]603.1.Are elevators properly maintained,and is the current certificate of inspection on the premises. a. b.606.3.Are approved standardized,pictorial signs posted adjacent to each elevator call station on all b. _ _ C floors reading, IN FIRE.ENIERGEM'v,DO Norr Usr:ELEVATOR,USE,ENI r STAIRS k C.606.7.Are keys for elevator car doors&fire department service kept in an approved location. C. d.315.3.3.Are elevator machine rooms maintained free from stored combustible material. d. e.[B]3005.1.Are elevator machine room doors maintained unobstructed at all times. e. 9.COMMERCIAL KITCHENS a.906.1. Are portable Class K fire extinguishers installed within 30 feet of cooking equipment. a. b.904.12.5.is the fire protection equipment inspected,tested&maintained as per Section 901.6. b. c.904.12.5.2.Are automatic fire extinguishing systems serviced at least every 6 months. e. d.904.12.5.3.Are fusible links&automatic sprinkler heads replaced annually. d. e.[RB]122-5.13.Are grease traps provided and installed as required by Village Code. f.[PC]1003.10.[RBI 122-6.Are grease traps properly maintained as per State and Village Code. g.[RB] 122-6.C., 122-9.Are all service,maintenance,&repair records for grease traps and related plumbing maintained on the premises as required by Village Code. g. 10.HEATING SYSTEMS a. [PM]603.1.Are all heating appliances properly installed&maintained in a safe working condition. a. ✓ _ b.[PM]603.2.Are all fuel-burning appliances&equipment connected to an approved chimney or vent. b. vdl' _ c.[PM]603.3.Are heating appliances maintained with proper clearances from combustible material. C. _✓ _ d.[PM]603.4.Are safety controls for fuel-burning equipment maintained in effective operation. d. .101 _ e.[PM]603.5.Is the fuel-burning equipment provided with adequate combustion&ventilation air. e. ✓ 11.MOTOR FUEL-DISPENSING FACILITIES&REPAIR GARAGES a.2303.2.Is an approved,labeled&readily accessible emergency disconnect switch provided a. in an approved location within 100'of,but not less than 20'from fuel dispensers. b.2304.3.4.Are dispenser operating instructions conspicuously posted on every fuel dispenser. b. _ c.2304.2.4.Are fuel-dispensers unobstructed&in clear view of the attendant at all times. C. _ �C d.2305.5.Are approved portable fire extinguishers complying with Section 906 with a minimum rating of d. _ _ x 2-A:20-B:C provided&located not more than 75' from pumps,dispensers&fill-pipe openings. e.2305.6.Are warning signs provided&posted within sight of each dispenser as per this section. e. _ V f.2305.7.Are weeds and other combustible materials kept at least 10'from fuel-handling equipment. f. _C g.2306.4.Are above-ground tanks provided with vehicle impact protection. g. h.2306.5.Are above-ground tanks provided with secondary spill containment. h. 12.HAZARDOUS MATERIALS(HAZ-MATS) a.407.2.Are S.D.S.Sheets for all haz-mats readily available on the premises. a. b.407.3.Are spaces and individual containers containing haz-mats properly labeled&identified. b. _ ✓ c.5004.2.Are stored haz-mats provided with approved secondary spill containment. C. ✓ _ d.5003.7.1.Are proper NO SMOKING signs provided as per this section. d. 13.MISCELLANEOUS a.403.1. Is an approved fire safety&evacuation plan prepared&maintained for the building/occupancy. a. _ _✓ _ b.405.1.Are emergency evacuation drills conducted at the intervals as specified in Table 405.2. b. _✓ _ c.405.5.Are records of emergency evacuation drills kept&maintained on the premises. C. �✓ _ d.505.1.Are approved address&building numbers properly placed&plainly visible from the street. d. e.506.1.Are approved key boxes(knox boxes)provided,properly located&equipped with the proper keys. e. _ _✓ _ f.703.1. Is all required fire-resistance rated construction properly maintained as per code. t g.703.1.Are openings through fire-resistance rated assemblies properly protected&maintained. g. h.5303.5.Are compressed gas cylinders&systems secured&safeguarded against damage&access. 11. �D ].5303.6.1.Are compressed gas cylinder caps or collars in place at all times except when tanks are in use. i. 14.GENERAL HOUSEliEEPING a.Good b.Fair c. Inadequate ' ^ d.Poor INSPECTOR: Z' "� DATE: 9— t -t- -3- Re,,,scd 6/1/2024 Report of Inspection / Test ���REPROIITrfC, Quarterly NFPA 25 �� 08-29-2025 Conducted by:Craig Lewis C� Property i Hallenbeck Learning Center-Cerebral Palsy Calculated Fire Protection Co., Inc. Westchester 2510 Route 44,Suite 2 ' ' 1186 King Street Hallenbeck Learning Center Salt Point NY 12578 Rye Brook NY 10573 845-677-5201 Danny Graham Service@calculatedfire,com Print Date:08-29-2025 Report of Inspection / Test General Questions OWNER SECTION Is the building occupied? 123 Yes Has the occupancy classification,hazard of contents, O Yes ❑ No and/or storage method remained the same since the ❑ No ❑ NA last inspection? ❑ NA Are all fire protection systems in service? O Yes Has the system remained in service without O Yes O No modification since the last inspection? ❑ No ❑ NA ❑ NA VALVE AREA Are all check valves externally inspected,operating O Yes Are the gauges on system showing normal water supply O Yes properly,and are in good condition? ❑ No pressure? ❑ No O NA ❑ NA Have the mechanical waterflow alarm devices passed 0 Yes Are valves identified with proper signage? O Yes tests by opening inspector's test connection/bypass ❑ No ❑ No connection with alarms actuating and flow observed? ❑ NA ❑ NA ALARMS Are alarms and supervisory devices not damaged? O Yes ❑ No ❑ NA FIRE DEPARTMENT CONNECTION Is the FDC plainly visible and easily accessible with caps O Yes Is the FDC check valve free of leaks and is the visible O Yes and plugs in place and undamaged? ❑ No piping supplying the FDC undamaged? ❑ No O NA ❑ NA Is the FDC identification sign(s)in place? O Yes ❑ No Q NA MAINTENANCE Was a valve status test conducted after opening any 2) Yes closed valve? ❑ No ❑ NA WET VALVE Is the alarm valve and associated trim free from physical D Yes Is the trim in correct(open or closed)position? O Yes damage? ❑ No ❑ No ❑ NA ❑ NA Is there no leakage in the retarding chamber or drains? O Yes ❑ No ❑ NA Copyright 2025 Inspect Point Page 2 of 4 Report of Inspection / Test E�Er,REPROtE�T�o Quarterly NFPA 25 08-29-2025 Conducted by:Craig Lewis Property www.calculatedfire.com Hallenbeck Learning Center-Cerebral Palsy Calculated Fire Protection Co., Inc. Westchester 2510 Route 44,Suite 2 (845)617-5201 1186 King Street Hallenbeck Learning Center Salt Point NY 12578 Rye Brook NY 10573 845-677-5201 Danny Graham Service@calculatedfire.com Print Date:08-29-2025 MAIN DRAIN FLOW TESTS System Initial Static Residual Static Seconds to Flow Did waterflow Are results Return to Observed? alarm comparable Initial Static operate? to previous test? W-Basement 80 70 80 1 Yes Yes Yes INSPECTORS TEST CONNECTION W-Basement (Wet) Location Description Time Reported? Smooth Easily Signs? Pass? to Orifice Accessible Alarm (seconds) R�sel TV Yes Yes Yes Yes Yes VALVES W-Basement (Wet) Valve Easily Stems #of Description Location Type Size Secured Open Accessible Signs Exercised Lubricated Turns Supply Bsmt OS&Y 6" Monitored Yes Yes Yes Yes Yes Control Bsmt Butterfly 4" Monitored Yes Yes Yes Yes Yes Copyright 2025 Inspect Point Page 3 of 4 QReport of Inspection / Test `Q�����REPROTf�l�oyc 08-29-2025 Conducted by:Craig Lewis Property www.calculatedfire.com Hallenbeck Learning Center-Cerebral Palsy Calculated Fire Protection Co.,Inc. Westchester 2510 Route 44,Suite 2 ' 45)611-5201 1186 King Street Hallenbeck Learning Center Salt Point NY 12578 Rye Brook NY 10573 845-677-5201 Danny Graham Service@calculatedfire.com Print Date:08-29-2025 Inspector Signature I state that the information on this form is correct at the time and place of my inspection,and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted. Inspector Name Signature Date Completed Craig Lewis 2025-08-29 Copyright 2025 Inspect Point Page 4 of 4 Report of 25spection / Test ����EEREPROTE�rZoyc 08-29-2025 Conducted by:Craig Lewis Property www.calculatedfire.com Hallenbeck Learning Center-Cerebral Palsy Calculated Fire Protection Co., Inc. Westchester 2510 Route 44,Suite 2 i 1186 King Street Hallenbeck Learning Center Salt Point NY 12578 Rye Brook NY 10573 845-677-5201 Danny Graham Service@calculatedfire.com Print Date:08-29-2025 Deficiencies- General Questions None Deficiencies-General Wet System Questions None Deficiencies-W-Basement None Deficiencies- Inspectors Test Connection None Deficiencies-Valves None Copyright 2025 Inspect Point Page 1 of 4 2 BUILDING .; g . REPORTS I . Fire Alarm Systems INSPECTIDN Cerebral Palsy - Hallenbeck Bldg 1186 King Street Purchase, NY 10577 914-384-4060 Building Contact: Danny Graham Title: Manager Company: Everon Contact: Calvin Powe Title: Inspector Inspection Date: May 20, 2025 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards.The subsequent pages of this report provide performance measurements,listed ranges of acceptable results,and complete documentation of the inspection.Whenever discrepancies exist between acceptable performance standards and actual test results,notes and/or recommended solutions have been proposed or provided for immediate review and approval. EXECUTIVE SUMMARY Generated by: BuildingReports.com Building Information Cerebral Palsy-Hallenbeck Bldg Contact:Danny Graham 1186 King Street phone:914-384-4060 Purchase,NY 10577 United States of America Fax: Mobile: Email: Inspection Performed By Everon Inspector:Calvin Powe Everon LLC Phone:914-327-6925 6 Skyline Dr. Hawthorne,NY 10532 Fax: United States of America Mobile: Email:calvin.powe@redhawkus.com System Control Unit Manufacturer:Est Inspection Date:05/20/2025 IDC Style: Model Number:io 500 Install Date:02/02/2017 SLC Style: Software Version: Version Date:08/03/2017 NAC Style: Location:Basement Disconnect Location: Disconnect Type: Current Protection: Inspection Summary Total Items Serviced Passed Failed/Other Category Qty % Qty % Qty % Qty % Control 3 3.85% 3 100.00% 1 33.33% 2 66.67% Initiating 73 93.59% 1 1.37% 1 100.00% 0 0.00% Supervisory 2 2.56% 2 100.00% 2 100.00% 0 0.00% Totals 78 100% 6 7.69% 4 66.67% 2 33.33% Certification Everon Page 1 of 16 Download Date;07/10/2025 Executive Summary Company:Everon Building:Cerebral Palsy-Hallenbeck Bldg Inspector:Calvin Powe Contact:Danny Graham Everon Page 2 of 16 Download Date:07/10/2025 Executive Summary DISCREPANCY REPORT Deficiency, Impairment, and Observation Generated by: BuildingReports,com The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type.The description of the problem is provided and where appropriate,code references are listed for your convenience.Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included. Building: Cerebral Palsy - Hallenbeck Bldg Items listed for Recall or Replacement/Upgrade Device Type Manufacturer Model Number Date Qty No recalled items found during this inspection. Building: Cerebral Palsy - Hallenbeck Bldg Control Panel: 2 Discrepancies ScanlD Location Problem Address Reference CONTROL Battery 33089279 Basement Fail test 2 33089282 Basement Fail test 2 Everon Page 3 of 16 Download Date:07/10/2025 Discrepancy Report PROPOSED SOLUTIONS REPORT Generated by: BuildingReports.com The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report.Provide a check mark where indicated to approve repairs listed within the report.Items listed as T/M are available for repair on a Time and Materials basis. Building: Cerebral Palsy- Hallenbeck Bldg Control Panel: 2 ScanlD Location Solution Model# Cost Fix CONTROL Battery 33089279 Basement Replace battery PS-12180 F2 T/M ❑ 33089282 Basement Replace Battery PS-12180 F2 T/M ❑ Customer WO/PO#: Internal WO/PO#: Total:T/M • (none) (none) Everon Page 4 of 16 Download Date:07/10/2025 Proposed Solutions Report INSPECTION & TESTING Generated by: BuildingReports.com The Inspection&Testing section lists all of the items inspected in your building.Items are grouped by Passed or Failed/Other.. Items are listed by Category.Each item includes the services performed,and the time&date at which testing occurred. Building: Cerebral Palsy - Hallenbeck Bldg Control Panel: 1 - Est io 500 Device Type Location Service Time Date PASSED Control Control Panel Basement Tested 1:21:04 PM 05/20/2025 Initiating Waterflow Switch Basement Tested 1:16:00 PM 05/20/2025 Supervisory Tamper Switch Basement Tested 1:15:01 PM 05/20/2025 Tamper Switch Basement Tested 1:20:54 PM 05/20/2025 UNTESTED Initiating CO Detector Main level day room CO Detector Basement Entry CO Detector Basement by FACP CO Detector Attic Duct Detector Basement open area.unit 1 Duct Detector Basement open area.unit 3 Heat Detector Main level bathroom Heat Detector Main level kitchen rec.rm Heat Detector Main level men's rm Heat Detector Main level women's rm Pull Station Main level Day Room Everon Page 5 of 16 Download Date:07/10/2025 Inspection&Testing Device Type Location Service Time Date UNTESTED(continued) Initiating(continued) Pull Station Main level corridor attic entry Pull Station Main level corridor by reception Pull Station Main level corridor by rm 3 Pull Station Main level main lobby Pull Station Main level side exit foyer Pull Station Basement Entry Pull Station Attic Top Of Stair Smoke Detector Main level corridor by side exit Smoke Detector Main level Board rm 6 Smoke Detector Main level Corridor by rm 14 Smoke Detector Main level Day rm skylight Smoke Detector Main level Day rm. Smoke Detector Main level Day rm. Smoke Detector Main level Day rm. Smoke Detector Main level Day rm. Smoke Detector Main level Main lobby Smoke Detector Main level Office 14 Smoke Detector Main level Room 1 Smoke Detector Main level Room 12 Smoke Detector Main level Room 8 Smoke Detector Main level Server room Smoke Detector Main level corridor by board rm Smoke Detector Main level corridor by pantry Smoke Detector Main level corridor by reception Smoke Detector Main level corridor by rm 3 Everon Page 6 of 16 Download Date:07/10/2025 Inspection&Testing Device Type Location Service Time Date UNTESTED(continued) Initiating(continued) Smoke Detector Main level corridor by rm 8 Smoke Detector Main level main lobby Smoke Detector Main level reception Smoke Detector Main level room 10 Smoke Detector Main level room 11 Smoke Detector Main level room 13 Smoke Detector Main level room 2 Smoke Detector Main level room 3 Smoke Detector Main level room 4 Smoke Detector Main level room 5 Smoke Detector Main level room 7 Smoke Detector Main level room 9 Smoke Detector Main level side Exit foyer Smoke Detector Main level toilet Smoke Detector Main level Mens toilet by pantry Smoke Detector Basement Open Area left Smoke Detector Basement Open Area left Smoke Detector Basement Open Area left Smoke Detector Basement Open Area left Smoke Detector Basement crawl space Smoke Detector Basement crawl space Smoke Detector Basement open area Smoke Detector Basement open area by FACP Smoke Detector Basement open area left Smoke Detector Basement open area left Everon Page 7 of 16 Download Date:07/10/2025 Inspection&Testing Device Type Location Service Time Date UNTESTED(continued) Initiating(continued) Smoke Detector Basement open area right Smoke Detector Basement open area right Smoke Detector Basement open area right Smoke Detector Basement open area right Smoke Detector Attic Open Area Smoke Detector Attic Open Area Smoke Detector Attic Open Area Smoke Detector Attic Open Area Smoke Detector Attic Sky Light Building: Cerebral Palsy - Hallenbeck Bldg Control Panel: 2 Device Type Location Service Time Date FAILED/OTHER Control Battery Basement Tested 1:21:18 PM 05/20/2025 Battery Basement Tested 1:21:34 PM 05/20/2025 UNTESTED Initiating Heat Detector Main level back office Heat Detector Basement boiler rm Everon Page 8 of 16 Download Date:07/10/2025 Inspection&Testing SERVICE SUMMARY Generated by: BuildingReports.com The Service Summary section provides an overview of the services performed in this report. Building: Cerebral Palsy - Hallenbeck Bldg Device Type Service Quantity PASSED Control Panel Tested 1 Tamper Switch Tested 2 Waterflow Switch Tested 1 Total 4 FAILED/OTHER Battery Tested 2 Total 2 UNTESTED CO Detector 4 Duct Detector 2 Heat Detector 6 Pull Station 8 Smoke Detector 52 Total 72 Grand Total 78 Everon Page 9 of 16 Download Date:07/10/2025 Service Summary BATTERY & POWER SUPPLY TESTING Generated by: BuildingReports.com The Battery&Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems.Items are grouped by Passed or Failed/Other. Building: Cerebral Palsy - Hallenbeck Bldg Control Panel: 2 Battery Rated Rated Post Tested Type Location Ah Volts Pre Test Test Min Ah Ah FAILED/OTHER Sealed Lead Acid Basement 18amp 12v Sealed Lead Acid Basement 18amp 12v Everon Page 10 of 16 Download Date:07/10/2025 Battery&Power Supply Testing INVENTORY & WARRANTY REPORT Generated by: BuildingReports.com The Inventory&Warranty Report lists each of the devices and items that are included in your Inspection Report.A complete inventory count by device type and category is provided.Items installed within the last 90 days,within the last year,and devices installed for two years or more are grouped together for easy reference. Building: Cerebral Palsy- Hallenbeck Bldg Device or Type Category %of Inventory Quantity Battery Control 2.56% 2 CO Detector Initiating 5.13% 4 Control Panel Control 1.28% 1 Duct Detector Initiating 2.56% 2 Heat Detector Initiating 7.69% 6 Pull Station Initiating 10.26% 8 Smoke Detector Initiating 66.67% 52 Tamper Switch Supervisory 2.56% 2 Waterflow Switch Initiating 1.28% 1 Building: Cerebral Palsy - Hallenbeck Bldg Control Panel: 1 - Est io 500 Type Qty Model# Description Install Date IN SERVICE-5 YEARS TO 10 YEARS Edwards Heat Detector 1 2838 Fixed Temperature 03/17/2016 Pull Station 1 SIGA-270 02/02/2017 Pull Station 5 270 Single Action 02/02/2017 Pull Station 1 270- Single Action 02/02/2017 Smoke Detector 1 SIGA2-PS Photoelectric 03/17/2016 Smoke Detector 1 Siga2PS Photoelectric 03/17/2016 Everon Page 11 of 16 Download Date:07/10/2025 Inventory&Warranty Report Type Qty Model# Description Install Date IN SERVICE-5 YEARS TO 10 YEARS(continued) Edwards(continued) Smoke Detector 2 siga2PS Photoelectric 03/17/2016 Est Control Panel 1 io 500 02/02/2017 Duct Detector 1 SIGA-SD Photoelectric 02/02/2017 Duct Detector 1 SIGA-SD Photoelectric 02/02/2017 Heat Detector 1 HRS-2 02/02/2017 Heat Detector 2 HRS2 02/02/2017 Pull Station 1 SIGA-270 Single Action 02/02/2017 Smoke Detector 6 SIGA2-PS 02/02/2017 Smoke Detector 1 siga-ps 2 02/02/2017 Smoke Detector 26 SIGA2-PS Photoelectric 02/02/2017 Smoke Detector 15 siga-ps 2 Photoelectric 02/02/2017 Kidde CO Detector 4 02/02/2017 Lansdale Tamper Switch 1 djw12 02/02/2017 System Sensor Tamper Switch 1 33089262 02/02/2017 Waterflow Switch 1 wfd40 02/02/2017 Building: Cerebral Palsy - Hallenbeck Bldg Control Panel: 2 Type Qty Model# Description Install Date IN SERVICE-3 YEARS TO 5 YEARS Power-Sonic Battery 2 PS-12180 F2 Sealed Lead Acid 01/03/2022 IN SERVICE-5 YEARS TO 10 YEARS Everon Page 12 of 16 Download Date:07/10/2025 Inventory&Warranty Report Type Qty Model# Description Install Date IN SERVICE-5 YEARS TO 10 YEARS(continued) Edwards Heat Detector 2 2838 Fixed Temperature 03/17/2016 Everon Page 13 of 16 Download Date:07/10/2025 Inventory&Warranty Report ZONE ADDRESS REPORT Generated by: BuildingReports.com The Zone Address Report lists all of the devices and items that have an individual address,or are grouped together under a common zone.The device type,location,and description are included for your reference. Building: Cerebral Palsy - Hallenbeck Bldg Control Panel: 1 - Est io 500 Address Device Type Location Type ScanID ZONE/CIRCUIT: 1 001 Smoke Detector Main level Room 1 Photoelectric 32784993 002 Smoke Detector Main level reception Photoelectric 32764992 003 Smoke Detector Main level room 2 Photoelectric 40318099 004 Smoke Detector Main level room 3 Photoelectric 40318100 005 Smoke Detector Main level room 4 Photoelectric 40318101 006 Smoke Detector Main level room 5 Photoelectric 32784977 007 Smoke Detector Main level Board rm 6 Photoelectric 32784994 008 Smoke Detector Main level side Exit foyer Photoelectric 32784988 009 Smoke Detector Main level room 7 Photoelectric 43876318 010 Smoke Detector Main level Room 8 Photoelectric 32784997 011 Smoke Detector Main level room 9 Photoelectric 32784996 012 Smoke Detector Main level room 10 Photoelectric 32784995 014 Smoke Detector Main level room 11 Photoelectric 36248016 015 Smoke Detector Main level Room 12 Photoelectric 40318097 016 Smoke Detector Main level room 13 Photoelectric 40318098 018 Smoke Detector Main level Mens toilet by pantry Photoelectric 32784999 019 Smoke Detector Main level toilet Photoelectric 32784998 020 Smoke Detector Main level Server room Photoelectric 43876316 021 Smoke Detector Main level Office 14 Photoelectric 36248015 Everon Page 14 of 16 Download Date:07/10/2025 Zone Address Report Address Device Type Location Type ScanlD ZONE/CIRCUIT: 1 (continued) 022 Smoke Detector Main level Corridor by rm 14 Photoelectric 32784984 023 Smoke Detector Main level corridor by reception Photoelectric 32784991 024 Smoke Detector Main level corridor by rm 3 Photoelectric 32784990 025 Smoke Detector Main level corridor by pantry Photoelectric 32784989 026 Smoke Detector Main level corridor by side exit Photoelectric 32784987 027 Smoke Detector Main level corridor by rm 8 Photoelectric 32784986 028 Smoke Detector Main level corridor by board rm Photoelectric 32784985 029 Smoke Detector Main level Main lobby Photoelectric 36248017 030 Smoke Detector Main level main lobby Photoelectric 33089260 032 Smoke Detector Main level Day rm. 33089269 033 Smoke Detector Main level Day rm. 33089292 034 Smoke Detector Main level Day rm. 33089291 035 Smoke Detector Main level Day rm. 33089295 038 Smoke Detector Attic Open Area Photoelectric 45685537 039 Smoke Detector Attic Open Area Photoelectric 45685536 040 Smoke Detector Attic Open Area 45685535 041 Smoke Detector Attic Open Area 45685534 042 Smoke Detector Attic Sky Light Photoelectric 45685533 043 Smoke Detector Basement open area left Photoelectric 40318084 044 Smoke Detector Basement Open Area left Photoelectric 40318091 045 Smoke Detector Basement Open Area left Photoelectric 40318092 046 Smoke Detector Basement Open Area left Photoelectric 43876281 047 Smoke Detector Basement open area right Photoelectric 40318090 048 Smoke Detector Basement open area right Photoelectric 40318089 049 Smoke Detector Basement open area by FACP Photoelectric 43876289 050 Smoke Detector Basement open area right Photoelectric 40318088 Everon Page 15 of 16 Download Date:07/10/2025 Zone Address Report Address Device Type Location Type ScanlD ZONE/CIRCUIT: 1 (continued) 051 Smoke Detector Basement open area right Photoelectric 40318087 052 Smoke Detector Basement open area left Photoelectric 40318096 053 Smoke Detector Basement Open Area left Photoelectric 40318085 054 Smoke Detector Basement crawl space Photoelectric 40318094 055 Smoke Detector Basement crawl space Photoelectric 40318093 056 Duct Detector Basement open area.unit 1 Photoelectric 40318095 057 Duct Detector Basement open area.unit 3 Photoelectric 33089284 058 Smoke Detector Basement open area Photoelectric 40318086 059 Smoke Detector Main level Day rm skylight 33089270 126 Pull Station Main level main lobby Single Action 32784982 127 Pull Station Main level Day Room 32784983 128 Pull Station Main level corridor by reception Single Action 32784978 129 Pull Station Main level corridor by rm 3 Single Action 32784979 130 Pull Station Main level side exit foyer Single Action 32784980 131 Pull Station Main level corridor attic entry Single Action 32784981 132 Pull Station Attic Top Of Stair Single Action 45685538 133 CO Detector Attic 43876767 135 CO Detector Main level day room 43876266 137 CO Detector Basement Entry 43876275 138 CO Detector Basement by FACP 43876267 139 Waterf low Switch Basement 33089262 140 Tamper Switch Basement 33089263 141 Tamper Switch Basement 33089267 142 Pull Station Basement Entry Single Action 33089268 Everon Page 16 of 16 Download Date:07/10/2025 Zone Address Report NE'N YO. STATE DEPARTMENT OF HEALTH Report on Test and Maintenance Bureau of Public Water Supply Protection of Backflow Prevention Device For the year ?0?'5 initial test- complete entire form sm Annual test-Complete Part A only Please use a separate form for each device. Block Lot Account No. County Public Water Supply N/A Westchester Jeolia - - Location of Device hi j1ding HallenBeck Bldg out,5ije Pit by EMnt-Qf Facility Name 1186 King St Rye Brook 10573 —_ _-- ---- Address zip Street City Type C� RPZ Model Size (in inches) Serial Number T Device Manufacturer DCV 0.75 73609 Information attS Differential Pressure Line Pressure Check Valve No. 1 Check Valve No.2 Relief VaIA m Leaked Leaked ❑ Opened at psid Date Test Closed tight Vs:.7 Closed tight M ���D��� �� Y before repair Pressure dro across first check valve 9-psid Repaired by Name Describe Lic# repairs and Date repaired: materials used ❑❑ �❑ M D Final Closed tight Closed tight Opened at psid Date M D m Y test M Pressure drop across first check valve psid Type of Service: (check one) Water Meter Number Meter Reading yp Other eptune 94775194 ❑ Domestic(❑ Fire ❑ Remarks (Describe deficiencies bypasses,outlets before the device,connections between the device and point of entry.missing or inadequate airgaps,etc. Certifica n:This device meets,❑does NOT meet,the requirements of an ac eptab ir 'n ent device at the time of tesing. I hereby certify the foregoing data to be correct. 1 2�- / / re V vF bi e Expiration Date Print Name Certifieffester No. Propertyowner's (orowner's agent) certification that test was performed: G r' f f oE�f /�t1�/'✓'�I�F c`��/l�C Signature �Telephone Print Name To be completed by the design engineer or architect C Certification that installation is in accordance with the approved plans- or water supplier.) I hereby certify that this installation is in accordance with the approved plans. NYS DOH Log# Name Title Date -- M D 1r — License Number Phone( ) Describe minor installation changes Representing Address City State ZlP Signature --- -Ive one supplier within 30days of the testing device. NOTE:Send one completed copy to the designatedwater eealth mmediartmtelyef device nt sfails`,est and repai spcannot immediately be made. Noti own and DOH-1013(9/91) NEW YORE STATE DEPARTMENT OF HEALTH Report on Test and Maintenance Bureau of Public Water Supply Protection of Backflow Prevention Device For the year 2025--- Initial test- complete entire form Please use a separate form for each device. [XD Annual test-complete Part A only Lot Count Block Public Water Supply Account No. y N/A Westchester Jeolia Location of Device Facility Nam�­IallenBeck Bldg _ )I fildinq 1186 King St Rye Brook 10573 — Address zipStreet City ❑� RPZ Model Size (in inches) Serial Number Type Device Manufacturer = DCV 6 126633 Information Watts Differential Pressure Line Pressure_ Q Psi Check Valve No. 1 Check Valve No.2 Relief Val ve Leaked 0 Leaked = Opened at `- psid Date t_S11 Test Closed tight ? Closed tight 110 I�M D Y before repair Pressure drop across first check valve '� O psid Repaired by Nape Describe Lic# repairs and Date repaired: materials used ❑� m Y Final Closed tight Closed tight Opened at psid Date m m m test M D Y Pressure drop across first check valve psid Water Meter Number Meter Reading Type of Service: (check one} ❑ Domestic )p Fire ❑Other Remarks (Describe connections between the device and point of entry.missing or inadequate airgaps,etc.) deficiencies:bypasses,outlets before the device, Certification:This deviceIhe foregoing does data T correct t e requirements an a cep able nt 'nment device at the time of tesing. I hereby certify 9 ` ' ig e Expiration Date Print Name CertifiedTester No. t)certification that test was performed: Propertyowner's (orowner's agen � r Ica J'itr r� _/�V1�i"r_`•^!�rtr�k' ( )TTelephone ( v C Title Signature Print Name To be completed by the design engineer or architect Z Certification that installation is in accordance with the approved plans. or water supplier.) I hereby certify that this installation is in accordance with the approved plans. NYS DOH Log## Name Title Date YLicense Number Phone( ) M p -- Describe minor installation changes Representing Address City State Zip Signature NOTE:Send one completed copy to the designated health department representative and one copy to the water supplier within 30 days of the testing device. Notify owner and water supplier immediately if device fails test and repairs cannot immediately be made. DOH-1013(9/91) SEW YORf< STATE DEPARTMENT OF HEALTH Report on Test and Maintenance 3ureau of Public Water Supply Protection of Backflow Prevention Device For the year 2025 — (� Initial test- comPlete entire form � Annual test-Complete Part A only Please use a separate form for each device. Block Lot Account No. bounty Public Wa ter Supply N/A Westchester ✓eolia Location of Device HallenBeck Bldg Cellar Facility Name Rye Brook 10573 ------- 1186 King St Address City zip — Serial Number Street T e RPZ Model Size (in inches) 002528 Device �/lattsfacturer yp �] DCV 2 Information Vv Differential Pressure Line Pressure .Psf Check Valve No. Check Valve No.2 Relief V ve T 1 � Jan II Leaked Leaked opened at v" psid Date 1 C L�p Test Closed tight Closed tight M D before repair Pressure drop ac oss first check valve, psid Repaired by Name Describe Lic# repairs and Date repaired: materials m m [U, used M D m Final Closed tight Closed tight Opened at psid Date M D y M D test Pressure drop across first check valve psid Type of Service: (check one) Meter Reading yp ❑Other Water Meter Number Domestic [I Fire (Describe deficiencies:bypasses,outlets before the device.connections between the device and point of entry,missing or inadequate airgaps,etc Remarks ❑does NOT meet,the requirements o an acc pt b c ntai ment device at the time of tesing. Certifica ion:This device meets, I hereby certify the foregoing data to be correct. Igna e Expiration Date CertifiedTester No. Print Name tification that test was performed: Propertyowner's (orowner's agent)cer 8 N kv Telephone Title — - S' nature Print N me To be completed by the design engineer or architect + Certification that installation is in accordance with the approved plans. or water supplier.) I hereby certify that this installation is in accordance with the approved plans. NYS DOH Log# Name Title D at e M D Y License Number Phone( ) — Describe minor installation changes Representing Address City State Zip Signature supplier within 30days of the testing device. NOTE:Send one completed copy to the designated health department reprosentative and one copy to the water Notify owner and water supplier immediately if device fails test and repairs cannot immediately he made. DOH-1013(9/91) BUILDIN � 1YRTMENT VI L E OF RY �f1tPOK II AUG 19 2025 938 KING ET RYE BRO NY 10573 -0 VILLAGE OF RYE BROOK € ov B�.lil_nING nEPARTMENT FIRE INSPECTION / OPERATING PERMIT APPLICATION FOR OFFICE USE ONLY:Fee Paid: $ —P� (�Inspection Date&Time: — I . FEE SCHEDULE: Re-inspection Date&Time: Triennial & Private School Annual Inspection: =$450.00 Public Assembly Annual Inspection: <100 People=$525.00/>100 People=$775.00 Application,dated: is hereby made to the Building Inspector of the Village of Rye Brook NY,requesting that a Fire Inspection be conducted at the building and premises listed below for the purpose of issuing a Permit to Operate the business, private school and/or place of public assembly in conformance with the Code of the Village of Rye Brook,the New York State Uniform Fire Prevention & Building Code, Title 19 NYCRR Part 1201, and all other applicable local, County, State & Federal laws, rules & regulations,as per detailed statement described below. 1186 King Street (Hallenbeck Bldg) 1. Address: SBL: Zone: 2. Business/Occupancy Name:Cerebral Palsy of Westchester NYS Use Class: 3. Property Owner: Cerebral Palsy of Westchester Address: Phone# Cell# email: 5. Business Owner: Address: Phone# Cell # email: 6. Emergency Contact: Dan Graham Address: Phone# 914-937-3800 x407Ce11# 914-384-4060 email: Danny.graham(aD_cpwestchesterorg 7. Inspection Escort: Dan Graham Title: Phone#: Cell#: email: S. Provide a brief description outlining the current and/or intended use of the property: Office space 9. List all Hazardous Materials: 10. Occupant Load: Existing: 69 Proposed: Other: 11. Date&Disposition of Previous Fire Inspection: 8/20/24 ❑ Pass ❑ Fail 1 6/1/2024 M This application must include the notarized signature(s) of the legal owner(s) of the above mentioned property, in the space provided below. Any application not bearing the legal property owner's notarized signature(s) shall be deemed null and void, and will be returned to the applicant. STATE OF NEW YORK ) COUNTY OF WESTCHESTER ) as: Linda Kuck ,being duly sworn, deposes and states that he/she is the applicant above named, (print name of individual signing application) and further states that he/she is the legal owner of the property to which this application pertains,or that he/she is the Executive Director ,for the legal owner and is duly authorized to make and file this application. That all (indicate architect,business owner,attorney,agent,etc.) statements contained herein are true to the best of his/her knowledge and belief,and that any work performed or use conducted at the above captioned property will be in conformance with the details as set forth and contained in this application and in any accompanying approved plans and specifications,as well as in accordance with the New York State Uniform Fire Prevention &Building Code,the Code of the Village of Rye Brook and all other applicable laws,ordinances and regulations. Sworn to before me this Sworn to before me this i Cl day of 1 (� , 20�7� day of , 20 —?7 —i� otary P blic No ry Pu iF nature of Property Owner i ature of Applicant Print Name of Property Owner Print Name of Applicant STEPHANIE RUSSO-PASTiLHA STEPHANIE RUSSO-PASTiLHA Notary Public,State of New York Notary Public,State of New York No.01 RU613651 9 No.0 1 RU613651 9 Qualified in Westchester County Qualified in Westchester County Commission Expires Nov.7,20:2.5 Commission Expires Nov.7,20.;;P—s^ 2 6/1/2024