HomeMy WebLinkAboutFire Detection/Suppression System 2006 THE RYE TOWN HILTON SYSTEM CERTIFICATION TEST AND INSPECTION INFORMATION r- ti 111 71 PJIT ROLF JENSEN &ASSOCIATES PROFESSIONAL ENGINEERS, P.C. FIRE PROTECTION CONSULTANTS March 30, 2006 Mr. Michael J. Izzo Building & Fire Inspector Village of Rye Brook 938 King Street Rye Brook, NY 10573 Dear Mr. Izzo This letter is to certify that all fire detection and suppression systems within the Rye Town Hilton have been fully tested and found to be in working order with very few exceptions. All systems meet or exceed the requirements of the Codes of the State of New York in effect at the time of their original completion. Any exceptions, defects, deficiencies or malfunctions have been or are in the process of being repaired. Attached to this letter are reports from the two sprinkler companies, one that services the wet and dry system (A & P Rainaldi) and the second that services the Viking Fire Cycle III system (United Fire Protection). Also attached is the report from the fire alarm company Fire Systems Inc. RJA is still working to complete a report detailing the findings of its non-intrusive egress survey conducted on the Rye Town Hilton located in Rye Brook, New York. The report will detail deficiencies and their remedies. Once the report is complete, the owner and management of the Rye Town Hilton will schedule a meeting with the Building Department of the Village of Rye Brook to discuss progress. Sincerely, ROLF JENSEN & ASSOCIATES, INC. Reviewed by: Edward B. Armm, SET Michael Nicoletta, A.I.A. Senior Consultant Operations Manager EBA:eba Attachments: Test and Inspection report from A & P Rainaldi, Inc. Test and Inspection report from United Fire Protection Corp. Test and Inspection report from Fire Systems, Inc. ItEbA01 mi-RyeHilton 03-30-60-02 pan 1ICCT 7I CT CTDCCT CI IITC 1nA n,M.Ivn Alv IMn111c a1COS RC7n CAV a1 7 aaC aa71 03/30/2006 03:26 FAX 9145790019 A P RAINALDI INC 16001 No: 227 A & P RAINAL.DI, INC 8 Via Fax 9 1 WC LIC#472-RC LIC#P28:-PC LIC#275 Re: Z 1 2 4115 Z,G•"7 r PO Box 624 White Plains NY 10603 PH 914 949-1919 Rye Town Hilton FX 914 579-0019 699 Westchester Ave Rye Brook, NY 10573 Attu: Ed Armn Transmittal From: Lori Rainaldi Date 3/30/2006 Project: Total Pages 7 Copies of Sprinkler Reports for your records Please feel free to call me with any questions. Thank you. Respectfully, Lori Rainaldi Form for Inspection, Testing and Maintenance of Fire Sprinkler Systems F AL ::PRIN"L� AS,-3 IRTU:)K W4C. Information on this form covers the minimum requirements of NFPA 25-1992 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. Separate fortes are available to inspect,test and maintain fire pumps and water tanks. Additional forms are also available for standpipe and hose systems,private fire service mains, water spray fixed systems and foam-water sprinkler systems. More frequent inspection,testing and maintenance may be necessary depending o e con ' Qns of the occt nd the water supply. Owner: ---r � DW A Owner's Address: Property Being Inspected: -- Property Address: 15v Date of Inspection: This inspection is (check one); ❑ Daily ❑Weekly ❑Monthly O Quarterly ❑ Semiannual ❑ Annual 0 Third Year 0 Fifth Year Note.- All questions are to be answered Yes,No,or Not Applicable. All"No"answers are to be explained in the comments portion of this form. All responses refer to..the current inspection performed on the date shown above. Part I - Owner's Section (To be answered by the Owner or Occupant.) A. Is the building Occupied? es O No O N/A B. Has the occupancy classification and hazard of contents remained the same since the last inspection?,,.6-Yes ❑No O N/A C. Are all fire protection systems in service?,Axes O No O N/A D. Has the system remained in service without modification since the last inspection? Yes 0 No 0 N/A E. Was the system free of actuations of devices or alarms since the last inspection?$Yes O No O N/A Part H- Inspector's Section A.Inspections 1.Daily,or weekly if low temperature alarms are installed Enclosures around dry-pipe,preaction or deluge valves maintaining a minimum of 401 F? ❑Yes O No,.4N/A 2.Weekly Inspection Items A.Preaction and Deluge Valves: B.Dry-Pipe Valves: 1.Free from physical damage? 0 Yes 0 No,,dN/A 1.Free from physical damage? O Yes ❑NoA�N/A 2.Trim valves in appropriate(open or closed)position? ❑Yes O No.i N/A 2.Trim valves in appropriate 3,No leakage from valve seat? O Yes ❑No4NIA (open or closed)position? ❑Yes El No�N/A 4.Electrical components in service? 0 Yes 0 No Abj/A 3.No leakage from intermediate chamber? O Yes 0 NoAN/A C.Relief port cn reduced pressure backflow prevention assemblies not continuously discharging? O Yes O No4WJq/A 3.Weekly inspection items which can be performed monthly if the items are electrically supervised or secured with locks A.Gauges on dry,preaction and deluge systems in good condition and showing normal air and water pressure? ❑Yes O No-�N/A B.Control valves: �'" 1.In normal(open or closed)positfi n?. es O No O N/A 2.Sealvi,locked r supervised?^Yes 0 No O NIA 3.AccessibleWes 0 No ❑N/A 4.Provided with appropriate wenches? O Yes O NcOM/A 5.Free from external leaks? 0-Xes 0 No 0 N/A 6.Provided with appropriate identification?dyes O No 0 N/A C.Isolation valves on backflow prevention assemblies in open position? O Yes ❑NcAN/A 4.Monthly Inspection Items JJ A.Proper number and type of spare sprinklers?X�•Yes 0 No O N/A B.Sprinkler wrench with spare sprinklers?jXes O No O N/A C.Gauges on wet-pipe system in good condition and showing normal water supply pressure?Ayes O No O N/A D. Alarm devices free from physical damage and all electrical connections secure?4Yes ❑No ❑N/A E.Alarm Valves: 1.Gauges indicating normal supply water pressure? 0 Yes ❑No&&/A 2.Free from physical damage? ❑Yes ❑No-44 A 3.Valves in appropriate(open or closed)position? Q Yes O No 4 4.No leakage from retarding chamber or alarm drains? 0 Yes O MANIA F.Sprinkler Pressure Regula,�ti(Qg Control Valves: 1.In open position?Z-Yes O No 0 N/A 2.Not leoaking?ICYes 0 No ❑N/A 3,Maintaining downstream pressure per design cn a Ia?A&Yes O No ❑N/A 4.In good condition with handwheels not broken? s O No O N/A 01992 National Fire Sprinkler Association,P.O.Box 1000,Patterson,NY 12563 Sheet I of 3,Printed 7/92 ZOOC(1] ONI IQ'IVNIVH d V 6T006L5fT6 XVd 9Z:80 900Z/09/90 4.Monthly Inspection Items(Continued) G.Fire Department Connections:, 1.Visible and accessible?,,WLyes O No 0 N/A 2.Couplings and swivels not damaged and rotate smoothly?kes 0 No 0 N/A 3.Plugs or caps in place and undamaged? es ❑No Q N/A 4.Gaskets in place and in good con ition? es ❑No Q N/A 5.Identification sign(s)in place? Yes ❑No Q N/A 6.Check valve is not leaking?fdYes 0 No 0 N/A 7. Automatic drain valve in place and operating properly? �les ❑No ❑N/A (Note: 1f plugs or caps are not in place, inspect the interior for obstructions and verify that the valve clapper is operational over its full range.) S.Quarterly Inspection Item Hydraulic nameplate,if provided,securely attached to riser and legible? 0 Yes O N0ACN/A 4.Annual Inspection Items A.Visible sprinklers: B.Visible pipe: 1.Free of corrosion?A(yes O No 0 N/A 1.In good condition?,es 0 No O N/A 2.Free of obstructions to spray atterns?pwz 0(ves 0 No O N/A 2.Free of mechanical damage?Ai yes O No O N/A 3.Free of foreign aterials?A-Yes ❑No O N/A 3.Not leaking?,E-TXes Q N 0 N/A 4.Free of paint? Yes 0 No ❑N/A 4.No external corrosio .�Xes Q No O N/A 5.Free of physical damage? Yes ❑No O N/A 5.Properly aligned?^ es ❑No O N/A 6.No external loads?01Yes 0 No ❑N/A C.Visible pipe hangers and seismic braces not damaged or loose?ALYes 0 No 0 N/A D.Adequate heat available to areas where wet sprinkler piping is located? LK Yes 0 No 0 N/A(Must be done before cold weather.) 5.Annual,or every llfth year for valves which can be reset without opening: Interior of dry-pipe,preaction and deluge valves passed internal inspection? 0 Yes Q No O(N/A 6.Fifth Year Inspection Items A.Alarm valves and their associated strainers,filters and restriction orifices passed internal inspection? ❑Yes O No 4/A B.Check valves Internally inspected and all parts operate properly,move freely and are in good condition? Q Yes 0 No p(NIA C.Strainers,filters,restricted orifices and diaphragm chambers on dry-pipe, preaction and deluge valves passed internal inspection? ❑Yes ❑No*/A B.Testing The following tests are to be performed at the noted intervals. Report any failures on Part III of this form. 1.Quarterly Tests A.Sprinkler system main drain test: 1.Record Static Pressure to-opsi and Residual Pressure_.e!!f psi. Was flow observed? Q Yes 0 NoXN/A 2.Are results comparable to pressures from last test? O Yes ❑Nof 8(N/A B.Waterflow alarm devices passed tests? 1.Inspectors test connection opened?(wet-pipe when not in freezing weather)CR(Yes ❑No 0 N/A 2.Bypass connection opened?(wet-pipe systems in freezing weather,dry-pipe,preaction,or deluge). ❑Yes O No PAN/A 3.Alarms actuated?ixYes Q No Q N/A Was flow observed?ct Yes ❑No 0 N/A C.Control Valves(except OS&Y and gear-operated indicating butterfly valves)opened until spring or torsion is felt in the rod,then closed back one-quarter turn? O Yes Q No aLN/A D.Priming water level passed test in dry-pipe and preaction systems? ❑Yes Q NoAJN/A E.Low air pressure signal in dry-pipe and preaction systems passed test? 0 Yes O NoAN/A 2.Semiannual Test Quick opening.devices passed test? ❑Yes O No jZ N/A 3.Annual Tests 1-' A.Are all sprinklers in service dated 1920 or later?OC-Xes O No ❑N/A B.Fast Response sprinklers in service for less than 20 years?� ❑Yes (aNciwe l r/A If"no"test sample now and every 10 years. C.Standard sprinklers in service for less than 50 years?-LTYes Q No 0 N/A 1f"no"test sample now and every 10 years. D.Specific gravity of antifreeze correct? ❑Yes Q NoveEN,/A E.All control valves operated through full range and returned to normal position? O Yes Q NoXN/A F.Preaction and deluge valves full flow trip test:(except deluge valves where water can't be discharged) (Be sure to test all systems at the same time which are designed to operate simultaneously in case offire.) 1.Water discharge from all nozzles unimpeded? ❑Yes 0 No A�N/A 2.Pressure reading at hydraulically most remote nozzle-,ZPsi. 3.Residuid pressure reading at valve _� psi. Was flow obs��TT��'ed? 0 Yes ❑No 1/A 4.Are above readings comparable to design values? ❑Yes ❑No 18-1+1/A 5,Manual activation devices passed test? O Yes ❑No ZVA 6.Automatic air pressure maintenance devices passed test? ❑Yes ❑No QUA 01992 National Fire Sprinkler Association,P.O.Box 1000,Patterson,NY 12563 Sheet 2 of 3,Printed 7/92 £00 2 ONI IQ'IVNIva d d 6T006L56T6 %V.3 LZ:£0 900Z/0£/£0 3.Annual Tests(continued) G.Dry-pipe valve partial flow trip test: 1.Record initial air pressure i, 2.Record initial water pressu psi. 3.Record tripping air pres a psi. 4,Record tripping tim (sec.). 5.Are above results comparable to previous tests? O Yes ❑No J�N�A H.Automatic air maintenance devices on dry-pipe and pre]EA ' systems passed test? D Yes 0 No.dNIA I. Backflow devices passed backflow test? 0 Yes O No J. Backflow devices passed full flow test? O Yes ❑No K.All sprinkler pressure regulating control valves passed full flow test? O Yes D Nod]4iA 4.Dry-pipe full flow trip test to be done every third year. A.Dry-pipe valve full flow trip test: 1.Record initial air pressure ps' 2.Record initial water pressure psi. 3.Record tripping air pressure psi and tripping time (sec.).. 4,Was water delivered to in ectors test connection? Cl Yes D No.49,N/A 5.Are above results comparable to previous tests? ❑Yes D No WMA 5.Tests to be done every fifth year. A.Extra High,Very Extra High and Ultra High Temperature sprinklers tested? O Yes D No Z1/A B.Gauges checked against calibrated gauge or replaced? ❑Yes D NoAN/A C.Maintenance: 1.Regular Maintenance Items A.If sprinklers have been replaced,were they proper replacements?All�yes 0 No ❑N/A B.Air leaks in dry-pipe system resulting in pressure loss more than 10 psi/week repaired? D Yes O No XN/A C.Dry-pipe systems being maintained in dry condition? O Yes ❑No;l/A D.Were any of the following discovered? O Yes ONo ❑N/A ff yes,conduct an obstruction investigation and flush the system. 1.Defective intake screen for pumps taking suction from open sources. 2.Obstructive material discharged during waterflow tests. 3.Foreign materials found in dry-pipe valves,check valves or pumps. 4.Heavy discoloration of water during drain test or plugging of inspectors test connection. 5.Plugging of sprinklers found during activation or alteration, 6.Plugging found in piping dismantled during alterations. 7.Failure to flush yard piping or surrounding public mains following new installation or repairs. 8.Record of broken mains in the vicinity. 9.Abnormally frequent false-tripping of dry-pipe valves. 10.System is returned to service after an extended period out of service(greater than one year). 11.There is reason to believe the system contains sodium silicate or its derivatives. 2.Annual Maintenance Items A.Operating stem of all OS&Y valves lubricated,completely closed,and reopened? O Yes ❑NoAiN/A B.Interior of dry-pipe,preaction and deluge valves cleaned? 0 Yes O Na /A C,Low points drained in dry-pipe,preaction and deluge systems prior to the onset of freezing weather? D Yes D NaN/A D.Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup? O Yes O No fN/A Part�II(II -- Cornments y "No"a wers,te{t fa�jures or other problems found with the sprinkler system mu explain d here.) F Part IV - Inspector's Information A $'P KA NA1.Di, INCH Inspector: dK Company: Plumbing-tavac•SOnkler-83CWd Ow Prsverlbw :ompany's Address: 914 949-1919 certify that the information on this form is correct at the time and plact;df my inspection,and that all equipment tested at this time was left in opera'o al tion upon completion of this inspection except as noted in Part III above. Signature of Inspector @1992 National Fire Sprin ociation,P.O.Box 1000,Patterson,NY 12563 Sheet 3 of 3,Printed 7/92 f00ln ONI IQ'IVNIVH d V 6T006LSVT6 XYd 8Z:£0 900Z/0£/£0 Form for Inspection, Testing and Maintenance of Fire Sprinkler Systems ASSMLArMft,INC. Information on this form covers the minimum requirements of NFPA 25-1992 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. Separate forms are available to inspect,test and maintain fire pumps and water tanks. Additional forms are also available for standpipe and hose systems,private fire service mains, water spray fixed systems and foam-water sprinkler systems. More frequent inspection, testing and maintenance may be necessary depending on t conditio f the occupa a the water supply. Owner Owner's Address. Property Being Inspected: L-00,10 V%NAI POC4,1, Property Address: Date of Inspection: �� L h► aLk This inspection is (check one): O Daily O Weekly ❑Month y O Quarterly O Semiannual O Annual O Third Year O Fifth Year Note: All questions are to be answered Yes,No,or Not Applicable. All"No"answers are to be explained in the comments portion of this form. All responses refer tathe current inspection performed on the date shown above. Part I - Owner's Section (To be answered by the Owner or Occupant.) A. Is the building occupied? Yes O No O N/A B. Has the occapaney classification and hazard f contents remained the same since the last inspection? Yes O No ❑N/A C. Are all fire protection systems in service?oes ❑No O N/A D. Has the system remained in service without modification since the last inspection? ,Yes ❑No ❑N/A E. Was the system free of actuations of devices or alarms since the last inspection?4-Xes U No O N/A Part II - Inspector's Section A.Inspections 1.Daily,or weekly if low temperature alarms are installed Enclosures around dry-pipe,preaction or deluge valves maintaining a minimum of 40'F?soql Yes O No O N/A 2.Weekly Inspection Items A.Preaction and Deluge Valves: B.Dry-Pipe Valves: 1 ' 1.Free from physical damage? O Yes O No&/A 1 l.Free from physical damage? 'es 0 No O N/A 2.Trim valves in appropriate(open or closed) sition? ❑Yes O No AGl N/A 2.Trim valves in appropriate 3.No leakage from valve seat? 0 Yes O No JWLN'/A (open or closed)position? &-Yes O No 0 N/A 4.Electrical components in service? O Yes O No A 3.No leakage from intermediate chamber?AKYes ❑No O N/A C. Relief port on reduced pressure backflow prevention assemblies not continuously discharging? O Yes O No X(N/A 3.Weekly inspection items which can be performed monthly if the items are electrically supervised or secured ,gh locks A.Gauges on dry,preaction and deluge systems in good condition and showing normal air and water pressure?ALYes 0 No ❑N/A B.Control valves: 1.In normal(open or closed)position? Yes ❑No ❑N/A 2.Sealed,locked or supervised? Xes 0 No O N/A 3. Accessible?0-Yes ❑No 0 N/A 4.Provided with appropriate wf enches? ❑Yes ❑No jdN/A 5.Free from external leaks? O-Kes ❑No O ljf/A 6.Provided with appropriate identification? Yes 0 No O N/A C.Isolation valves on backflow prevention assemblies in open position? O Yes ❑No il:�UA 4.Monthly Inspection Items A.Proper number and type of spare sprinkler QlYes 0 No O N/A B. Sprinkler wrench with spare sprinklers?4&Xes ❑No ❑N/A C.Gauges on wet-pipe system in good condition and showing normal water supply p�ry ssure?k(es O No O N/A D.Alarm devices free from physical damage and all electrical connections secure?c2Yes 0 No ❑N/A E.Alarm Valves: 1.Gauges indicating normal supply water pressure? ❑Yes ❑No JdLAN/A 2,Free from physical damage? ❑Yes 0 No 4N/A 3.Valves in appropriate(open or closed)position? O Yes 0 No 29N/A 4.No leakage from retarding chamber or alarm drains? ❑Yes O No AJN/A F.Sprinkler Pressure Regulating Control Valves: 1.In open position?Ot.Yes ❑No O N/A 2.Not leaking?JiPks D No O N/A 3.Maintaining downstream pressure per design criteria?AYes ❑No 0 N/A 4.In good condition with handwheels not broken? Ikes 0 No 0 NIA ©1992 National Fire Sprinkler Association,P.O.Box 1000,Patterson,NY 12563 Sheet 1 of 3,Printed 7/92 900[A 3uI IQ'IVUIVH d V 6T006L9tT6 YU 8Z:£0 900Z/0£/£0 4.Monthly Inspection Items(Continued) G,Fire Departmelit Connections: 1.Visible and accessible?,Xyes O No ❑N/A 2.Couplings and swivels not damaged and rotate smoothly? Wyes O No O N/A 3.Plugs or caps in place and undamaged? 4-Yes ❑No O N/A 4.Gaskets in place and in good con hion? EPYes 0 No D N/A 5.Identification sign(s)in place? es ❑No O N/A 6.Check valve is not leaking?4 yes 0 No O N/A 7.Automatic drain valve in place and operating properly?dyes 0 No ❑N/A (Note: If plug;,or caps are not in place, inspect the interior for obstructions and verify that the valve clapper is operational over its full range.) 5.Quarterly Inspection Item Hydraulic nameplate,if provided,securely attached to riser and legible? ❑Yes O No IO/A 4.Annual Inspection Items A.Visible sprinklers: B.Visible pipe: 1.Free of corrosion?A�Yes ❑No ❑N/A 1,In good condition?.6Yes D No D N/A 2.Free of obstructions to spray�Patterns?4Yes O No ❑N/A 2.Free of mechanical damage? GlfYes O No ❑N/A 3.Free of foreign aterials? J&Yes ❑No 0 N/A 3.Not leaking?Xyes 0 No ❑N/A 4.Free of paint? i s ❑No O N/A 4,No external corrosion? 2&es O No O N/A 5.Free of physical damage? Roes D No D N/A 5.Properly aligned? Yes ❑No O N/A 6.No external loads?4 Yes ❑No ❑N/A C.Visible pipe hangers and seismic braces not damaged or loose?oYes O No Q N/A D.Adequate heat available to areas where wet sprinkler piping is located? C1 Yes O No a(N/A(Must be done before cold weather.) 5.Annual,or every:3fth year for valves which can be reset without opening: Interior of dry-pipe,preaction and deluge valves passed internal inspection? O Yes O No-E%NIA 6.Fifth Year Inspection Items A.Alarm valves and their associated strainers,filters and restriction orifices passed internal inspection? D Yes ❑No fi!!�,//A B.Check valves internally inspected and all parts operate properly,move freely and are in good condition? ❑Yes 0 NoN/A C. Strainers,filters,restricted orifices and diaphragm chambers on dry-pipe, preaction and deluge valves passed internal inspection? 0 Yes ❑No�<N/A B.Testing The following tests are to be performed at the noted intervals. Report any failures on Part III of this form. 1.Quarterly Tests A.Sprinkler system main drain test: 1.Record Static Pressure(t2Q psi and Residual Pressure psi. Was flow observed? ❑Yes ❑No-dN/A 2.Are results comparable to pressures from last test? O Yes 0 No d.N/A B.Waterflow alarm devices passed tests? 1.Inspectors test connection opened?(wet-pipe when not in freezing weather) ❑Yes 2-<,No ❑N/A 2.Bypass connection opened?(wet-pipe systems in freezing weather,dry-pipe,preaction,or deluge).�Yes O No ❑N/A 3.Alarms actuated? Yes 0 No 0 N/A Was flow observed?AlY es O No 0 N/A C.Control Valves(except OS&Y and gear-operated in icating butterfly valves)opened until spring or torsion is felt in the rod,then closed back one-quarter turn? O Yes O No /A D.Priming water level passed test in dry-pipe and preaction systems?4Yes ❑No O N/A E.Low air pressure signal in dry-pipe and preaction systems passed test?4-Yes O No O N/A 2.Semiannual Test Quick opening devices passed test? ❑Yes ❑No R�N/A 3.Annual Tests A.Are all sprinklers in service dated I920 or later?46-Y-es O No ❑N/A �/�� B.Fast Response:sprinklers in service for less than 20 years? 0 Yes O No 4NIA If"no"test sample now and every 10 years. C.Standard sprinklers in service for less than 50 years?Ag.Yes ❑No 0 N/A If"no"test sample now and every 10 years. D.Specific gravity of antifreeze correct? ❑Yes D No EWA E.All control valves operated through full range and returned to normal position? 0 Yes D NoG!.N/A F.Preaction and deluge valves full flow trip test:(except deluge valves where water can't be discharged) (Be sure to test all systems at the same time which are designed to operate simultaneously in case of fire.) 1.Water discharge from all nozzles unimpeded? D Yes O Nq�N/A 2.Pressure reading at hydraulically most remote nozzle psi. 3.Residual pressure reading at valve "psi. as flow ob�frved? 0 Yes 0 No l(N/A 4.Are above readings comparable to des' values? 0 Yes O No M/A 5.Manual activation devices passed test? 0 Yes ❑No&SLA 6.Automatic air pressure maintenance devices passed test? ❑Yes O No 1/A 01992 National Fire Sprinkler Association,P.O.Box 1000,Patterson,NY 12563 Sheet 2 of 3,Printed 7/92 900[n DNI IQ'IVNIVU d V 6T006L56T6 XVd 6Z:£0 900Z/0£/£0 3.Annual Tests(continued) G.Dry-pipe valve partial flow trip test: 1.Record initial air pressure_�Opsi. 2.Record initial water pressure UD psi. 3.Record tripping air pressure�_ psi. 4.Record tripping time -' (sec.). S.Are above results comparable to previous tests? O Yes O NoRSN/A H.Automatic air maintenance devices on dry-pipe and preac�t' n systems passed test?/�Yes ❑No ❑N/A I. Backflow devices passed backflow test? O Yes O Nost�N/A J. Backflow devices passed full flow test? O Yes O No /A K.All sprinkler pressure regulating control valves passed full flow test? O Yes O No RN/A 4.Dry-pipe full flow trip test to be done every third year. A.Dry-pipe valve full flow trip test: 1.Record initial air pressure 2,Record initial water pressure psi. 3.Record tripping air press tti+� psi and tripping time (sec,).. 4.Was water delivered to inspectors test connection? O Yes O No.erN/A 5.Are above results comparable to previous tests? O Yes O No QUA 5.Teats to be done every fifth year. A.Extra High,Very Extra High and Ultra High Temperature sprinklers tested? U Yes ❑NoZN/A APJ N B.Gauges checked against calibrated gauge or replaced? ❑Yes O No /A C.Maintenance 1.Regular Maintenance Items ,.,/� A.If sprinklers have been replaced,were they proper replacements? O Yes O No i-A&A B.Air leaks in dry-pipe system resulting in pressure loss more than 10 psi/week repaired? Yes (3 No O N/A C,Dry-pipe systems being maintained in dry condition?dyes O No O N/A D,Were any of the following discovered? O Yes 994!o O N/A If yes,conduct an obstruction investigation and flush the system. 1.Defective intake screen for pumps taking suction from open sources. 2.Obstructive material discharged during waterflow tests. 3,Foreign materials found in dry-pipe valves,check valves or pumps. 4.Heavy discoloration of water during drain test or plugging of inspectors test connection. 5.Plugging of sprinklers found during activation or alteration, 6.Plugging found in piping dismantled during alterations. 7.Failure to flush yard piping or surrounding public mains following new installation or repairs. 8.Record of broken mains in the vicinity. 9, Abnormally frequent false-tripping of dry-pipe valves. 10.System is returned to service after an extended period out of service(greater than one year). 11.There is reason to believe the system contains sodium silicate or its derivatives. 2.Annual Maintenance Items A.Operating stem of all OS&Y valves lubricated,completely closed,and reopened.) O Yes O No A�CNIA B.Interior of dry-pipe,preaction and deluge valves cleaned? O Yes O No /A C.Low points drained in dry-pipe,.preaction and deluge systems prior to the onset of freezing weather? D Yes 0 No�1/A D.Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup? O Yes ❑No /A Part III - Comments (Any"No"answers,test failures or other problems found with the sprinkler system must be explained here.) Part IV - Inspector's Information A ♦ F KAINALDI., INC. ►nspector; Company: Phxnbing-HVAC-sw+ridw•Ba*iow Prevention :ompany's Address: 914 949-1919 _certify that the information on this form is correct at the time and plact:of my inspection,and that all equipment tested at this time was left in ope: 13 na1 edition upon completion of this inspection except as noted in Part III above. Signature of Inspector CI"2 National Fare Sph'nkld Association,P.O.Box 1000,Patterson,NY 12563 Sheet 3 of 3,Printed 7/92 Looln DUI I(FIVNIVH d V 6T006L56T6 XV.3 6Z:£0 900Z/0£/£0 03/29/2006 13:38 FAX 908 688 0218 UNITED FIRE PROTECTIONZ 001 UNITED FIRE PROTECTION CORD WIT 07992 493 Lehig Avenue Uio , NewJee , 07083 (908)688-0300 FAX: (908)810.4949 � p / Q LI1IERY DAT` J09 tNAIAE SERVICE:TCKE 1 N0. (aO/�5'h��Q��Qt ALI Program Yes El No 1 N/A El ADDRESS (( 1=_CDR As Built Yes=: No CITY STATE ZIP Job No, TYPE OF SYSTEM TYPE OF CALL SYSTEM LEFT BILLING TECH CHARGE D FM-200 a NEW INSTALLATION PARTIALLY IN SERVICE L*1 SERVICE/REPAIR R FIRE ALARM ❑ REPAIR SYSTEM IN NORMAL OPERATION ❑ CONTRACT _T/H PPEACTION ❑ ADD ON ❑ OUT OF SERVICE I-3 WARRANTY _ D.T. ❑SPRINKLER ,YeINSPP-CTION = MANUFACTURER 8 MODEL# ❑ NON-BILLABLE #OF MEN ❑ HALON �_ ❑ CHECK OUT LILA cyc� REASON OTHER r c ❑ OTHER REV# EXTINGUISHER REPORT NUMBER:ER MATERIAL DESCRIPTION 71 - • '�.0 t�Ak �-.•. I REPORTED CUSTOMER PROBLEMS - DESCRIPTION OF WORK PERFORMED - ,~f c d S —L n r. (n h e, 01 n e S as pew. 1 Kp ja re ), 4h IMMEDIATE ACTION REQUIRED Q © G G p � C 71 DISPATCHED ERV EMAN'S SIGNATURE �71 M (75� is I; DEPARTED HORIZED SIGAM N TUR O CU3TOMER PRINT NAME OF SIGNER �I ^� DATE PRINT NAME OF SIGNEF, 03/29/2006 15:58 FAX 908 688 0218 UNITED FIRE PROTECTION Z 002 United Fire Protection Corporation PASIRPGI 493 Lehigh Avenue Page 1 of 3 Union, New Jersey 07083 January 1, 2004 Phone: 908-688-0300 . Fax: 908-688-0218 PRE-ACTION SYSTEM INSPECTION REPORT DATE: 3 y O CUSTOMER: I Ve TOW6_Hi 40A SITE: li-'es"jjer Ave _— r�oo� JV� &a573 Area(s) being protected: � Print Inspector(s) Names) & I.D.#: J- CS i�► OG 3`i`�0 Report to be filed with: Department Supervisor: Building Engineer: ✓ Fire Department: Building Manager: Other: T e of Actuation: (Fill the quantity) Manual Release: Photo Smoke: Ion Smoke: Heat Detectors:� Crossed Zone: (explain): Other: Control P nel: Quantity:` Modell _1f JZ Manufacturer: Vj t Serial #: Pre-Action Information: Valve Size: .� I Model: �- 1 Manufacturer: i/iJh S Compressor Information: U, in -M5 �- 03/29/2006 15:58 FAX 908 688 0218 UNITED FIRE PROTECTION Z 003 PASIRPG2 Page 2 of 3 January 1,2004 YES NO NA INSPECTION ( ( ) ( ) I. Were all proper personnel and authorities notified? ( ( ) ( ) 2. Is there a 24-hour call for service sticker on the control panel? ( ( ) ( ) 3. Is area free of any changes that might affect protection? ( ( ) ( ) 4. Are all devices securely mounted and unobstructed? 5. is there a riser diagram by control panel (NYC)? 6. is there a sequence of operation by control panel (NYC)? ( ) ( ) (-r 7. Does control panel have pre-action and MEA# sign (NYC)? DETECTION 1 . Were all detectors checked for operation per manufacturer's recommendation? 2. Did they function property? ( ) ( ) ( 3. Were all settings recorded? ( ) ( ) (-1` 4. Were all detectors cleaned where needed? 5. Were they replaced as needed? MAN UAL RELEASES ( ) ( ) { 1. Are all manual releases properly labeled? 2. Do they function properly? ( ) ( ) ( 3. Are they accessible in case of fire? GRAPHIC ANNUNCIATOR ( ) { ) ( 1. Was annunciator checked? 2. Did all lights work properly? CONTROL 1. Were all operating functions checked & function properly? 2. Were all supervisory functions checked & function properly? 3. Were batteries tested per manufacture's recommendations? Amps in Stand-by:� Amps in Alarm: ( ( ) ( ) 4, Were batteries functioning properly? ( { ) ( ) 5. Were batteries replaced as needed? Date Installed 6. Was alarm verification checked? 7. Was ground fault protection tested? ( ) ( ) ( 8. Is there a fuse cut out and is it labeled for pre-action? 9. Is there circuit breaker number and location on pre-action panel? 03/29/2006 15:58 FAX 908 688 0218 UNITED FIRE PROTECTION 1?1 004 PASIRPC3 Page 3 of 3 January 1,2004 YES NO NA AUDIBLE(5} & VISUAL(S} 1 . Do all indicating devices operate as per NFPA and/or Local AHJ? 2. Do all indicating devices have signs to show purpose? PRE--ACTION VALVE 1 . Was pre-action valve tripped? Dry Wet �r ( ( ) ( ) 2. Was water-flow test valve checked? Priming water press / 00 Static water press /d O 3. Was tamper valve checked and working properly? ( ( ) ( ) 4. Was low air pressure switch checked and working properly? Normal Air Presssure _ 'Mvs' Compressor On Pressure 35L Low Air Signal Pressure a_SSosi. INTERLOCKS AND AUXILIARY FUNCTIONS TESTING 1 . Building Tie-in 2. Central station - Company: Account Number: ( ) ( ( ) 3. Equipment shutdown 4. Other 5. Were all tested? {r) ( ) ( ) 6. Did they function properly? If interlocks cannot be tested, or there is not adequate interlocks, explain in detail below: Comments: ` ? Per /&,VA► Sr/S-�e rn. Total pages in this re ort: Customer Signature: Print Name: Title: Phone: Technician's name (print): Sim ,5� �Sk1 03/29/2006 15:59 FAX 908 688 0218 UNITED FIRE PROTECTION Z 005 Form for inspection,Testing and Maintenance(►t Preaction and Deluge Fire Sprinkler Systems InformaWn on tits form coveru the mtntmurn requirements of NFPA 2s4av for fire aprinkler systems canneded to dlstdbunorr Systems withou7supptamerital tanks or Ora pump&Separate forms ere available to Inspect,test and malnt„in fire pumps,water tanks and other fire pnotecon systems-More inspection,teong and maintenance may be necessary depending an tha andlllam of the o=oancy and the wdt-L suPPI'�; Owner's Phone Number Owners Add o c ProRn Being Evaluated' 'c its 1 e. e Address: pate rtOf Work 3 a All Sea refer to the currentworc IneaecUOn testingandmalntanarize) rformedan MIS dates_ 711is work la(check one): ,Monthly Quarterly A(Inual sp TMrd Year FMhYssr Notes:11 An questions arc to be answered Yes No w nrot AppACRb1e All No ar swers are to be explained in Part III of oils farm. 2!Inspeollon,Tilting and Maintenance are to be perfnrmetl whh Water er ppliC9(including fire pump%)in service,unlaas the impairment Dm=dur= F Cneoter 11 of NFPA 25 are fnrowetl. Y N �f N MIA Part I-Ownertis Section G.Annual tnapectlon Items(In addition to above Remal X A Proper number and type of spare sprinklers? :� A.is the bulldlftg accupieOccupied? B.Has the ocwpancy claaelficatton and hazard of 8.Visible sprink ors. contents remained the same since the last inspection? X 1,Free of corrosion and physical damage? C C,Are all the rite protection systems In service? 1 2 Free of obstructions to spray prattems? %< D.Has ills system reins netl in service without3.Free of foreign materials Incluomg paint? )! modification since the IaSt insc&CbOP? x 4.Liquid in afl glass bulb sprinklers? :C E Was the system free of actuation of devices or x C.Visible pipe: ale,rna since the last Inspection? 1-In good oenllnonlno erdamal corrosion? 2.No mechanical damage and no leaks? Owner or roprasentw&-e(print name) signature and Date 3.Property aligned and no external loans? ?C Part tit-Inspector's section Y N N!A D.Visible pipe hangers and Seismic braces not damaged or loose? A.Inepactions 1.Daily and Weekly Items E.Preaciion and deluge valves that need to be A.Control va3ver supwvlead with seals in opened to be reset passed internal Inspection? correct(open or dosed)pos(fion? F.Must be done be3lore epid weather ONE B.Valve endosurae maintaining at least 40F7 X 1.Adequate heat In areas with wet piping? X C.Gauges In good condition and Showing 2 Low temperature alarms functioning? . r.ortrrai air and water pressure? X 3 Pipe through ireezers hoe of ice otockage? X D.Backflow preventers: G.Has an internal inspection of the pipe baen performs q by 1.In correct(open Or closed)position? X removing the flushing connection antl one sprinkler near the ;.sealed,locked or supervised&accessible? end of a branch line within uta last 5 years? C 3_Relief port on RPZ device not discharging? (if the ariawar was'No-.eenauct an intemaf rnsppc 0n) IY For freezer syaterns,is tote gage near(he compressor reading B.Fifth Year Inspection Items(in addition to abavo tte its) the same as the gage rear the pnaac6on valve?� A.Check vatvga Internally inaparted and all parts Qpel its QnoPefIY. 4.Monthly Inspection!tarns(in addition to above Items) move freely end are in good condition-? A.Cor"l valves with loeka or electrical suparvialon B.Strainers,filters,reatrictsd crificaa and diaphragm in coned(open or closed)position? L^�= chambers passed Internal inspecliOrr? X S,Valves free tram physical damage.Wm valves in appropriate C.Preaction an deluge valves Ihat can be (open Or Closed)position,no laakage from valve seat, extemaily reset passed internal Inapeclton7 and all electrical components in service? B_Testing C.Sprinkler wrenen with spare sprinklers? The following tests are to be performed at the noted inter fors.Repcn 5-Quartarly Inspection item(In addYdon to above Items) any failures on Part IIi of this term. A.Pr"sure Reducing Valves:In open position,not leaking, 1.Quarterly Test malntalydng downstream pressure per design erlterla,and in A.Mechanical waterflow alarm devices passed tests oy 4ening good condition with handwheele not broken? the Inspect&!&test connection or bypass C01111 click B.Hydraulic namepiste(calculated syatams) with alarms actuating and tiow observed? li��---It securely attached to Baer and legible? S.Post indicating valves open`ad until Spring or torslor is fait C.Fore Department Connections: In the rod,than closed back one-quarter turn? 1 k Vrsible,acrsstble,couplings and swivels not damaged aria rotsta c Is the priming level correct and has the low I X smoothly,piuga or caps In place and undamaged,gaskets in place air pressure signal passed its test? and in good condition.Ident1faallon aian(s)in place,check valve ie D.Main drain test for system downstream of bac)dlCW Orpressure not(Baking,clapper la in place and operating proppp�eedridyyy and autam�aric reducing valve drain valve In place and operating properly? I—L_ 1 1.Racord State Predsure —Psi and Residual Pre3sure M. (if rwga erceps orp ,of In p)sca,inspect irtfarforfbr009(rucNons) 2.Was flew observed? f) Alarm devices free from physical damage? � S.Are results comparable to previous test? L Form 25-13X Page 1 of 2 03/29/2006 15:59 FAX 908 688 0218 UNITED FIRE PROTECTION Z 006 N NIA Y N NIA vi Items) FValve st On additlou to pravlorta items) 2.Annual Maint®nance items(In adtlltlon to pre offs A.operating stem of all OS??Y vatvas IUDrratcrd, MM visory Svdtc'tma indicate movmmeni? � completely Dosed,and reopened? ferflow alarm devices passed tests by ppenlol913.L pw Points dralnee Prior to me onset of rs test connection or bypass connection ( freezing weather? with alarms acwating and now observed? J C.Sprinklers and sp-y no&u protecting commercial(*oking 3,Annual Teats pn addklon to previous items) equipment and ventilating gystems replaced except Nr bulb—type A.Main drain test which show no signs of grease buNdup? 1.Record$tell-Presaure,psl and Residual Pfeesure el. r� 2.Waa flaw observed? X 3.Are results comparable to orevlous test? X Pert lIt-Comments(Any"No"dRswars,fast fatluras oroiher B.AM all sprinklers dated 1920 or IpterT �C problems found turf f the sprinkler system most be ezpleirr3d Hang. C.Fast response sprinklers 20 or mono years old replaced or Also,Hoff here any products pto cn the system Milt o t h eve been rh [r�Lr—fit'-- subJect of a rsceJl ar a replacementant proprem) suxesstully, F1 sample tested within last 10 y0e7 D Standard response sprinklers 50 or more Years oto re laced or sUgceS5 uUy Sample tested within last 10 years? >C� E,Standard response sprinklers 75 or more years old re )acted or successfully sample tested within last 5 years? X F,Dry-type Sprinkliem replaced o sucasssfully sample taatOd e9lIn the last 10 years? G.All control vslvee operated througn full range and ra"rad to normal position? H.Low t8mpennure alarms passed test? �- 1.Full slow trip teat(Not required when;tvatar can't be dlocharQad) (Test eiq systems fogather that wN oparato a)muRenaeusty�X �1.Dlacharge from all nuzzles unimpeded? 2 Pressure reading at hydraulically most remote name_,_pal. lve 4 Residues pressure reading at o decor al a Above rt.0dings comparable rA design valves? �`- 5 Manual Qcttvalion davicas passed test J.Automatic air maintenance devices on dry-papa and preacJon systems passed teat? — K Backflow devices passed bECMOW test? x M.Pressure radudng valves passed parbgl flow taxi? X 4.Tests to be done every fifth year. A Sponkiers rated above high temper-awre tested? S.Gages checked by calibrated gage or replaced? C.Pressure reducing valves passed full flow test? C.Maintenance 1.Regular Maintenance Items A.if serinkler5 have been replaced,were they proper replacements? B.Have low point drams been emptied'' G.If any of the fonowing were discovered,was an obstruction nvestigation¢anducted? �2/ II &plain rsason(s)and obstructlon inVastlgafioR findings in Part W 1,:)eeClive intake acreen on pump w,th auction from open sources 2,0baVUoWa material discharged during waterflow tests 3.Forelgn materials found In dry-pipe valvek,check valves of pumps 4.Foreign material In water during drain test or plugging of inapeetor's test connection 5.Plugging of pipe or sprinklers found during activation or alteration Part W-ins eCtor's Irtfarmatlon , t3.Failure to flush yard piping or surrounding public mains thawing Inspector. ,ryt C 4 CompaeY n z' 'Cl " new installation or repairs o 7.Record of brnkon mains In the vicinity Ctampanys Aderess: � r .� @,Abnormally frequent ialite-tripping of dry-pipe v8lvea I staff!that NB mfpmlatlon on this form is ColTeCt at U'istuna and place 9,system is returned to service after an extended 0960d aut of of er inspection,and that all mgpletion 0 tested al w1trIll! n e was lab In servitx(greater than one year) operatlanal condition upon completion pf fnls utepeCion except as notetl 10,There Is reason to believe the system cOntains 9001Um silicate In Part Ill above. or its dertvsttves or highly corrosive duxes In copper ploe-syAtems. G / 9 0.If contlltlons were found that required Signature of Irtepactor: �` prr� � a frusl4ng wag flushing of system conducted? LICen9e or Certification m (If appli�bla)'� -- Pogo 2 cif 2 Form 2S13JC 03/30/2006 16:45 9147691652 FSI PAGE 01 194 Grady Avenue SERVICE REaI3E5fi Nt PO,Box 56 _.. - Hawtharna Naxr...York 1A5 4056 t 914.769.8M•f.974.769.8364 Spoala tft in fNe dvxWn,sale vnd'amlca of *,vyinplhelndLffuySk?ce t966 SECUF CITY,FIRE ALARM,CCTV,,SOUND and GOMMUNIC,ATtONS SYSTEMS REQUIES ED BY CHPE O►F k1EC�UESt _1a31 41�... ROB . (914) 934-253Y CTR#3219 3 19 .LOB LOCATION _ INVOICE TO: (SAME AS JOB LOCATION UNLESS OTHERWISE INDICATED) HIL.TON RYE TOWN Sl :MI HIL.TON RYE TOWN 699 WEST- CFItrSTER AV F C RE DIRECTOR OF PROPERTY ...__. . 699 WESTCHESTER AVENLIE 699 WESTCHEFSTER AVENUE - RYE .BROOK, NY 10573 RYE BROOD(, NY 10573 J08 CONTACT ]TELEPHONE NO. DESCRIPTION OF PROBLEM: PERFORM COMPLETE JNSPECTION ON THE FIRE ALARM SYSTEM PER RED QUOTED PRICE FOR I..ABOR ONLY ^' REPAIR'S TO BE QUOTED VER MODEL ❑WARRANTY SUBMITTAL# MAKE SERIAL s➢t rl QUOTED TJ=CdN1CIAM. ___ DATA aN;+oe= © TIME&MATERIAL G)3N REPAIRS MADE: FK FURMED FULL FlTNCTION ],,IVE) INSPECTION ON THE ENTI�RE ALARNL5Y 'I TESTED ELEVATOR RECALL, FAX SHUTDOWN, OUTPUT TRIPS,CPNT AL STATION A.CTIVATIONS. ALL.DEVICES TESTED AS'SOCLiiTED WITH.THE FIRE ALARX S.XSTEM,.,TES SYSTEM LEFT IN. 'NORMAL' WORKING CONDITION. TESTED ALL ROOM (STAND-ALPINE) 9ROKE DETECT ORS. . .PLEASE SEE ATTACHED FOR PROBLEMS FOUND. QTY- -PART# PFIICE OTY, PART# PRICE _@ - @ PARTSNVORK REQUIRED FF1=L0.LABL7A: Licensed by the N.Y.5 Dwenment of Slate•#12tlO MIl DATE HOURS + HOURS = HOURS.* HR.= LABOR LABOR TRAVEL. TOTAL DATE COMPLETED PART& DATE HO'IRS fi HOURS = HOURS a HR._ _. SHIPPING --- - HANDLING LABOR TRAVEL TOTAL DATE HOURS + HOURS = HOURS 0 HR._ TAX �._ .... _..._... -- APAOUNT 03/30/2006 16: 45 9147691652 F5I PAGE 02 FIRE SYSTEMS, INC._INS F'ECTION SHEETS PAGE# 1 OF 1 Licensed by the N.Y.S. Department of State #12000076160 LEGEND: JOB: R' E TOWN HILTON DATE: 3/2716 TO 3130/6 PS: PULL STATION SD: SMOKE DETECTOR 4 WERTCHERTFR AVE TECHS: PAT D./JIM N./ROB b./ HD: HEAT DETECTOR _M E RlZnn.K. NY 10S73 _ AL K./JAY S./MIKE C./ DD: DUCT DETECTOR FS: FLOW SWITCH GERRY P. MM: MONITOR MODULE STAND-ALONE SMOKE DETECTORS CM: CONTROL MODULE NOT TIED TO FIRE ALARM PANEL DEVICE ROOM NUMBER ZONE AND/OR TYPE ADDRESS VOLT COMMENTS SD LOCAL 110VAC 476 NOT WORKING SD LOCAL 56 NOT WORKING $p LOCAL 362 NOT WORKING p LOCAL 380 NOT WORKING p LOCAL 350 NOT WORKING p LOCAL 384 NOT WORKING SD LOCAL 385 NOT WORKING SD LOCAL 386 NOT WORKING SD LOCAL. 256 NOT WORKING SD LOCAL 254 NO COVER Sp LOCAL 387 NOT WORKING D LOCAL 284 NOT WORKING SD LOCAL 629 NO POWER SD LOCAL 504 NOT WORKING SD LOCAL 501 NOT WORKING SD LOCAL 314 NOT WORKING p LOCAL 304 NOT WORKING SD LOCAL 328 NOT WORKING 03/30/2006 16: 45 9147691652 FSI PAGE 03 Site notes for contract: 3219 HILTON RYE TOWN SEMI 699 WESTCHESTER AVENUE RYE BROOK, NY 10573 SEMI-ANNUAL INSPECTION C N YOUR FIRE ALARM SYSTEM. TECH IS TO GET PRINTOUT ON LOCATION OF DEVICES 03/30/2006 16:45 9147691652 FSI PAGE 04 Professional Testing Testing Site: HILTON RYE TOWN SEMI 699 WEST.CHUSTER AV FIRE 61121.1 699 WESTCHLSTER AVENUE Page 1 RYE BROOK, NY 10573 ID Device Vocation Results WF OFFICE FRONT DESK CEILING [ Ok [ ]See Notes SD RYE WING A FL 1 BY RM 167 [Jfgk [ ]See Notes SD RYE WING A FL 1 BY RM 170 [;(0k [ ]See Notes SD RYE WING A FL 1 BY RM 171 [ /fOk [ ]See Notes SD RYE WING A FL 1 BY RM 173 [ ��k [ ]See Notes SD RYE WING A FL 1 BY RM 174 [ ok [ ]See Notes SD RYE WING B FL 1 BY RM 175 [ /fOk [ ]See Notes SD RYE WING B FL 1 BY RM 177 [ ofok [ ]See Notes SD RYE WING S FL 1 BY RM 179 [ /]Ok [ ]See Notes SD RYE WING B FL 1 BY RM 181 [/fOk ( ]See Notes SD RYE WING A FL 1 JCT. B/C ( �k ( ]See Notes SD RYE WING C FL 1 BY RM 149 [ ]Ok j ]See Notes SD RYE WING C FL. 1 BY RM 147 [ ,fok [ )See Notes SD RYE WING C FL 1 B FITNESS CENTER [ � [ ]See Notes SD RYE. WING C FL 1 BY RM 145 [ 10k [ ]See Notes SD RYE WING C FL 1 BY RM 143 [ 46 k [ ]See Notes SD RYE WING C FL 1 BY RM 142 JQ k [ ]See Notes SD RYE WING D 5L 1 ELEV LOBBY [ fk [ ]See Notes SD RYE WING D FL 1 PASS. E.M.R. [ • O'k [ ]See Notes SD RYE WING C FL 1 FITNESS CENTER (,�'Ok C ]See Notes SD RYE WING D FL 1 LL SERV.EMR [ '-k [ ]See Notes SD RYE WING C FL 1 FITNESS CENTER [ -,,/k [ ]See Notes SD RYE WING D FL 1 BY SERV ELEV ]See Notes SD RYE WING D FL 1 TELCO RM 1 [ k [ ]See Notes SD RYE WING D FL 1 TELCO RM 2 [ Ok ( ]See Notes SD RYE WING D FL 1 BY RM 140 [ Ok [ ]See Notes SD RYE WING D FL 1 BY RM 13$ [ X6k [ ]See Notes SD RYZ WING D FL 1 BY RM 104 [ ,,rok [ ]See Notes SD RYE WING D FL 1 BY RM 106 [ fik ( ]See Notes SD RYE WING D F.L. 1 BY RM 108 [/rOk [ ]See Notes SD RYE WING D FL 1 BY RM 109 [ ?r6lc [ ]See Notes SD RYE WING D FL .l BY RM 110 [ 4,ok [ ]see Notes SD RYE WING D FL 1 BY RM 112 [ ,,rok ( ]See Notes SD RYE WING D FL 1 BY RM 115 [ k [ ]See Notes SD RYE WING D FL 1 BY RM 116 j/I`Ok [ ] See Notes SD RYE WING D FL 1 BY RM 119 [ ,rbk [. ]See Notes SD RYE WING A FL 2 BY RM 265 [ i]'01c [ ]See Notes SD RYE WING A FL 2 BY RM 263 rOk [ ]see Notes SD RYE WING A FL 2 BY RM 261. [ ,rOk [ ]See Notes SD RYE WING A FL 2 BY RM 259 [ erlbk [ ]See Notes SD RYE WING A FL 2 BY RM 258 [ ,J'ok [ ]See Notes SD RYE WING B FL 2 BY RM 257 [ ,j"6k [ )See Notes SD RYE WING B FL 2 BY RM 255 [ ]See Notes SO RYE WING B FL 2 BY RM 253 [!rOk [ ]See Notes Sc RYE WING B FL 2 BY RM 281 [/rok [ ]See Notes SD RYE WING S FL 2 JCT. B/C ( /]�Ok [ )See Notes SD RYE WING C FL 2 BY RM 249 [ ]See Notes SD RYE WING C FL 2 BY RM 247 [.�]ok [ ]See Notes Contract No. 3219 03/30/2006 16:45 9147691652 FSI PAGE 05 law lip ll Professional Testing Testing Site: HILTON RYE TOWN SEMI 699 WESTCH:'',STER AV FIRE 61121. 1 699 WESTCH;i;,BTER AVENUE Page 2 RYE BROOK, NY 1.0573 ID Devicc Loe@tion ReSUItS SD RYE, WING C ='L 2 BY RM 245 [ �k (. ]See Notes SD RYE WING C FL 2 BY RM 244 [ 1Ok [. ]See Notes SD RYE WING C FL 2 BY RM 243 [ k [. ]See Notes SD RYE WING D FL 2 ELEV LOBBY [ �lOk [ ,] See Notes SD RYE WING D FL 2 MAIN LOBBY ( �Ok [ ]See Notes SD RYE WING D FL 2 BY RM 241. 6 k [ ]See Notes SD RYE WING D FL 2 2 SERV ELEV LOBBY [ k [ ]See Notes SD RYE WING D FL 2 BY RM 239 ( Ok [ ]See Notes SD RYE WING D FL 2 BY RM 237 E / k [ ]See Notes SD RYE WING D FL 2 BY RM 235 (/]Ok [ ] See Notes SD RYE WING D FL 2 BY RM 234 [ 'I k [ ]See Notes SD RYE WING D FL 2 BY RM 232 [ Ok [ ]See Notes SD RYE. WING E FL 2 BY RM 231 ( /fOk [ ]See Notes SD RYE WING E FL 2 BY RM 229 ' /1j"9 k [ ]See Notes SD RYE WING E FL 2 BY RM 221 (, �Ok [ ]See Notes SD RYE WING E FL 2 BY RM 225 [ /�Olc [ ]' See Notes SD RYE WING E FL 2 BY RM 223 [ / _Qk [ ] See Notes SD RYE WING E FL 2 BY RM 221 [ /�Ok [ ]See Notes DD ACS-6 RYE FAN RM FL 1 [ /rOk [ ]See Notes DD ACS-5 RYE FAN RM FL 1 [ /Ok [ ]See Notes DD ACS-7 RYE A WING CRAWL SPA ­fqk [ ]See Notes DD ACS-B RYE B WING CRAW_ SPA [ / Ok ( ]See Notes DD ACS-9 RYE C WING CRRW!, SPA [ / ok [ ]See Notes DD AC5-10 RYE D WING CRAWL SPA [ /fOk [ ]See Notes DD ACS-11 RY;S E WING CRAWL SPA ( f0lc [ ] See Notes WF RYE WING A FL 1 STAIR j /lQk [ ] See NoteS TS RYE WING A FL 1 STAIR [ -rOk [ 1 Sce Notes PS RYE WING A FL 1 BY RM 166 [ 4 k [ ]See Notes 2S RYE WING A FL 1 JCT. A/B [ /rOk [ ]See Notes PS RYE WING B FL 1 STR JCT B/C [ !fOk [ 'See Notes PS RYE WING B FL 1 JCT. B/C [ T'Ck [ ]See Notes WF RYE WING B FL 1. 3 WING STAIR [ XOk [ ]See Notes TS RYE WING B FL 1 STAIR [ ,(b k [ ]See Notes PS RYE WING C FL 1 FTTNESS CTR [ hole [ ]See Notes oS RYE WING D FL 1 ELEV LBY k [ ]Sec Notes PS RYE WING D FL 1 JCT. D/E [ /]�Ok ( ]See Notes PS RYE WING E FL 1 STR BY 1.1.9 [ �0lc [ ] See ?Votes WF RYE WING E FL 1 E WING STAIR ] See Notes TS RYE WING E FL 1 STAIR [ ,fok [ ]See Notes WF RYE WING A FL 2 A WING STAIR [/�Ok [ ]See Notes IS RYE WING A FL 2 STAIR [ n k [ ]See Notes PS RYE WING A FL 2 BY RV 266 [ -'Ok [ ;See Notes PS RYE WING A FL 2 JCT. B/C [ /r9k I ]See N0tQ5 WF RYE WING B FL 2 STR JCT. B/C [ Ok ( )See Notes TS RYE WING B FT. 2 JCT. S/C ////k [ ]See Notes PS RYE WING D FL 2 LOBBY STAIR [ pk [ ]See Notes P5 RYE WING D FL 2 JCT. D/E [ -C�k [ ]See Notes PS RYE WING E FL 2 BY RM 219 [ Ok [ ] See Notes Contract No. 3219 03/39/2006 16:45 9147691652 FSI PAGE 06 r Professional Testing Testj.nc Site: HILTON RYE TOWN SEMI mm 699 WESTCH]':STER AV FIRE 6112=. 1 699 WESTCHUSTER AVENUE Page 3 RYE BROOK, NY 10573 YD Device Location Results WF RYE WING E FL 2 STAIR [. -k [ ]See Notes TS RYE WING E FL 2 STAIR . / Ok ( ]See Notes PS RYE WING A CRAWL SPACE [ ]See Notes WF RYE WING A CRAWL SPACE BRANCH [ ,,10k ( ]See Notes TS RYE WING A CRAWL (BRANCH) [ �91c [ ]See Notes �f TS RYE WING A CRAWL (MAIN RISER) [ Olc [ ]See Notes TS RYE WING B CRAWL (CENTER) [ /bk [ ]See Notes PS RYE WING B CRAWL SPACE [ ]See Notes TS RYE WING B CRAWL B/C MAIN [ ]See Notes TS RYE WING B CRAWL B/C BRANCH [ -fOk [ ]See Notes ;or RYE WING c CRAWL SPACE B/C [ ]See Notes W= RYE WING D FIRE PUMP CRAWL SPACE [ ]See Notes WF RYE WING D CRAWL SPACE/GAS RM [ /fOk [ ]See Notes WF RYE WING E WEST MAIN CRAWL SPACE [ /]'Ok [ ]See Notes PS RYE WING E CRAWL SPACE [ ,�'Ok [ ]See Notes SD RYE WING A FL 3 BY RM 365 [ ''Ck [ ]See Notes SD RYE WING A FL 3 BY RM 363 [ ! Ok [ ]See Notes SD RYE WING A FL 3 BY RM 361 [/fOk [ ]See Notes SD RYE WING A FL 3 BY RM 359 [, /7Qk [ ]See Notes SD RYE WING A FL 3 BY RM 358 [ 'JOk [ ]See Notes SD RYE WING B FL 3 BY RM 357 [ 'f k [ ]See Notes SD RYE WING B FL 3 BY RM 355 [ 'JOk [ ]See Notes SD RYE WING B FL 3 BY RM 353 t [ ]See Notes SD RYE WING B FL 3 SY RM 381 [ [ ]See Notes SD RYE WING B FL 3 JCT. B/C Ok [ ]See Notes SD RYE WING C FL 3 BY RM 349 [ Ok [ ]See Notes SD RYE WING C FL 3 BY RM 347 [ fk [ ]See Notes Sc RYE WING C FL 3 BY RM 345 [ k [ ]See Notes SD RYE WING C FL 3 BY RM 343 [ ,]bk [ ]See Notes SD RYE WING C FL 3 BY RM 342 [ lrOk [ ]See Notes SD RYE WING D FL 3 ELEV LBY [ ,r6k [ ]See Notes SD RYE WING D FL 3 SERV ELEV LOBBY [ I,Ok [ ]See Notes SD RYE WING D FL 3 BY RM 339 [ i]'�Ok [ ]See Notes SD RYE WING D FL 3 BY RM 337 [ ,j"Q k [ ]See Note: SD RYE WING D FL 3 BY RM 336 [ �Ok [ ]See Notes SD RYE WING D FL 3 BY RM 334 [/rOk [ ]See Notes SD RYE WING D FL 3 JCT. D/E 0fQk [ ]See Notes SD RYE WING E FL 3 BY RM 331 C -Qk ( ]See Notes SD RYE WING E FL 3 BY RM 329 [ k [ ]See Notes SD RYE WING E FL 3 BY RM 327 [ OOk [ 3See Notes ,SD RYE WING E FL 3 BY RM 325 [ ]See Notes SD RYE WING E FL 3 BY RM 323 [ �'Ok [ ]See Notes SD RYE WING E FL 3 BY RM 321 [wok [ ]See Notes SD RYE WING A FL 4 TOP OF STAIR [/Tok [ ]See Notes SD RYE WING A FL 4 BY RM 466 [ 4-O)c [ ]See Notes SD RYE WING A FL 4 BY RM 463 [ 1"'g k [ ]SAe Notes SD RYE WING A FL 4 BY RM 461 [ �k [ ]See Notes SD RYE WING A FL 4 BY RM 459 [ �J k [ ]See Notes Contract Flo. 3219 03/30/2006 16: 45 9147691652 F5I PAGE 07 Professional Testing Testing SitE: FILTCN RYE TOWN SEMI 699 WESTCH';STER ,AV FIRE 6'�12 J.• J, 699 WESTCk1; ;S':ER AVENUE Page 4 RYE BROOK, NY 1,0573 ID Device Location Results SD RYE WING FL 4 BY RM 458 [ Ok ( ]See Notes SD RYE WING B FL 4 BY RM 457 [JOk [ ]See Notes SD RYE WING B FL 4 BY RM 454 [ "lk [ ]See NOtes SD RYE WING B FL 4 BY RM 453 [ Ok [ ]See Notes SD RYE WING B FL 4 BY RM 481 1410k [ ]See Notes SD RYE WING B FL 4 BY RM 482 [/fok [ ]See Notes SD RYE WING C FL 4 TOP OF STAIR B/C [/fok [ ]See Notes SD RYE [RING C FL 4 BY RM 449 [ /f Ok [ ]See Notes SD RYE WING C FL 4 BY RM 447 [Ik ( ]See Notes SD RYE WING C FL 4 BY RM 445 [ k [ ]See Notes SD RYE WING C FL 4 BY RM 443 [ /fOk [ ]See Notes SD RYE WING C FL 4 BY RM 442 1 jok k [ ]See Notes SD RYE WING D FL 4 ELEV .LOBBY [ [ ]See Notes SD RYE WING D FL 4 TOP OF STAIR 1Ok k [ ]See Notes SD RYE WING D FL 4 SERV ELEV LOBBY [ [ ]See Notes SD RYE WING D FL 4 TOP PASS ELEV SFAFT [ /fOk ( ]See Notes SD RYE WING D FL 4 BY RM 439 [ /f k [ ]See Notes SD RYE WING D FL 4 BY RM 437 [ 10k [ ]See Notes SD RYE WING D FL 4 BY RM 436 [ / k [ ]See Notes SD RYE WING D FL 4 BY RM 434 [ Ok ( ]See Notes SD RYE WING D FL 4 JCT. D/E [ �Ok [ ]See Notes SD RYE WING E FL 4 BY RM 431 [ /rok [ ]See Notes SD RYE WING E FL 4 BY RM 429 1, [ ]See Notes SD RYE WING E FL 4 BY RM 427 [ 4k [ ]See Notes SD RYE WING E FL 4 BY RM 425 [ ?Ok [ ]See Notes SD RYE WING E FL 4 BY RM 423 E k [ ]See Notes SD RYE WING E FL 9 BY RM 421 [ �Ok [ ]See Notes SD RYE WING E FL 4 TOP OF STAIR ]See Notes WF RYE WING A FL 3 A WING STAIR [ �k [ ]See Notes TS RYE WING A FL 3 STAIR [ ']Ok [ ]See Notes PS RYE WING A FL 3 BY STAIR [ --rOk [ ]See Notes PS RYE WING A FL 3 JCT. B/C [ ,fOk [ ]See Notes WF RYE WING B FL 3 B WING STAIR [ .,' k [ ]See Notes TS RYE WING B FL 3 STAIR [ k [ ]See Notes EIS RYE WING D FL 3 ELEV LOBBY [/rOk [ ]See Notes PS RYE WING D FL 3 JCT D/E [4Ok [ ]See Notes pS RYE WING E FL 3 BY RM 319 [ /'6k [ ]See Notes WF RYE WING E FL 3 STAIR [ -,r'Ok [ ]See Notes TS RYE WING E FL 3 STAIR [ 4k f, ]See Notes WF RYE WING A FL 4 A WING STAIR [ Ok [ ]See Notes TS RYE WING A FL 4 STAIR ( Al"Oh [ ]See Notes PS RYE WING A FL 4 BY RM 466 [ k [ ]See Notes PS RYE WING A FL BY RM 463 [/J [ ]See Notes SD RYE WING A FL BY RM 461 [ [ ]See Notes SD RYE WING A FL BY RM 459 [ /]�Ok [ ]See Notes SD RYE WING A FL BY RM 458 [ pk [ ]See Notes SD RYE WING B FL BY RM 457 [ j [ ]See Notes SD RYE WING B FL BY RM 454 [ k [ ]See Notes Contract No. 3219 03/30/2006 16:45 9147691652 FSI PAGE 08 .................... 'law= Professional Testing Testing Site: HILTON RYE TOWN SEMI 699 WESTCHii:STER AV FIRE 61121.1 699 WESTCHii;STER AVENUE Page 5 RYE BROOK, NY 10573 ID Device Location Results SD RYE WING B FL BY RM 453 [4pk [ ]See Notes SD RYE WING B FL BY RM 481 C Ok [ ]See Notes SD RYE WING B FL BY RM 482 ( j'0k [ ]See Notes SD RYE WING C FL 4 TOP OF STAIR B/C [ /rOk [ ]See Notes SD RYE WING C FL 4 BY RM 449 [ /fQk [ ]See Notes SD RYE WING C FL 4 BY RM 447 [/fOk [ ]See Notes SD RYE WING C FL 4 BY RM 445 [ /rOk [ ]See Notes SD RYE WING C FL 4 BY RM 443 [/.C'Ok [ ]See Notes SD RYE WING C FL. 4 BY RM 442 [. /�Qk [ ]See Notes SD RYE WING D FL 4 ELEV LOBBY [ IOk [ ]See Notes SD RYE WING D FL 4 TOP OF STAIR [ ,j'Q k [ ]See Notes SD RYE WING D FL 4 SERV ELEV ,LOBBY ( �O`k [ ]See Notes SD RYE WING D TOP PASS ELEV SHAFT jjlc [ ]See Notes SD RYE WING D FL 4 BY RM 439 [ //Ok [ ]See Notes SD RYE WING D FL 4. BY RM 437 [ i Ok [ ]See Notes SD RYE WING D FL 4 BY RM 436 [ /f�ok [ ]See Notes SD RYE WING D FL 4 BY RM 434 [ ,I'Qk [ ]See Notes SD RYE WING D FL 4 JCT D/E ]See Notes SD RYE WING E FL 4 BY RM 431 [ � Ok [ ]See Notes SD RYE WING E FIB 4 BY RM 429 [1�( k [ ]See Notes SD RYE WING E FL 4 BY RM 427 [ �Ok k [ ]See Notes SD RYE WING E FL 4 BY RM 425 [ k ( ]See Notes SD RYE WING E FL 4 BY RM 423 [ ( ]See Notes SD RYE WING E FL 4 BY RM 421 ( /rOk [ ]See Notes SD RYE WING E FL 4 TOP OF STAIR ( k [ ]See Notes WF RYE WING A FL 3 A WING STAIR ( Ok [ ]See Notes TS RYE A WING 5L 3 STAIR [ /!]Ok [ ]See Notes PS RYE WING A FL 3 BY STAIR [ �JOk ( ]See Notes PS RYE WING A FL. 3 JCT B/C [ /fQk [ ]See Notes WF RYE WING B FL 3 D WING STAIR (/'Qk [ ]See Notes TS RYE B WING FL 3 STAIR [ �Ok [ ]See Notes PS RYE WING D FL 3 ELEV LBY [ -,fQk [ ]See Notes PS RYE WING D FL 3 JCT D/E [ 4k [ ]See Notes PS RYE WING E FL 3 BY RM 319 [ , Qk [ ]See Notes WF RYE WING E FL 3 STAIR [�.k ( ]See Notes TS RYE WING E FL 3 STAIR [ ?k [ ]See Notes WE RYE WING A FL 3 A WING STAIR [ ,T'Qk ( ]See Notes TS RYE WING A FL. 3 STAIR [, O k [. ]See Notes PS RYE WING A FL 3 BY RM 466 [ �Ok [ ]See Notes PS RYE WING A FL 4 JCT B/C [ � [ ]See Notes WF RYE WING C FL 4 C WING STAIR k [ ]See Notes TS RYE C WING FL, 4 STAIR k [ ]See Notes PS RYE WING D FL, 4 LOBBY STAIR [ 3 SQ2 Notes PS RYE WING D FL 4 BY RM 408 Po [ ]SEe Notes PS RYE WING E FL 4 BY RM 419 ( [ ]See Notes WF RYE WING E TL 4 STAIR [ [ ]See Notes TS RYE WING E FL 4 STAIR [Qk [ ]See Notes SD WEST WING FL 5 ELEV MACH RM [ Ok [ ]See Notes Contract No. 3219 03/30/2006 16:45 9147691652 FSI PAGE 09 Professional Testing Testing Site: HILTON RYE TOWN SEMI 699 WFSTCH;i;STER AV FIRE 61121.1 699 WESTCH:;.STER AVENUE Page 6 RYE BROOK, NY 10573 ID Device Location Results SD WEST WING FL 5 ELEV LOBBY [ k [ ]See Notes SD WEST WING FL 5 BY RM 500 [ �k [, ]See Notes SD WEST WING FL 5 BY RM 526 [/rOk [ ]See Notes SD WEST WING F,L 5 BY RM 524 [ � k [ 19ee Notes SD WEST WING FL 5 BY RM 522 [ ,jOk [ ]See Notes SD WEST WING FL 5 BY RM 520 [/p k [ ]See Notes SD WEST WING FL 5 BY RM 516 i/JOk [ ]See Notes SD WEST WING FL 5 BY RM 516 [5r k [ ]See Notes SD BAGATELLE REAR AREA RM [ Ok [ ]See Notes SD BAGATELLE REAR AREA RM [/r k [ ]See Notes SD BAGATELLE REAR AREA RM 11c Ok [ ]See Notes SD BAGATELLE REAR AREA RM ( [ ]See Notes SD BAGATELLE FRONT RM [ k [ ]See Notes SD BAGATELLE FRONT CARPET STORAGE ( ,fOk [ ]See Notes HD SUB-BAGATELLE WALL PAPER STORAGE L �Ok [, ]See Notes HD SUB-BAGATELLE LEFT RM AREA [/Ok [ ]See Notes HD SUB-BAGATELLE CENTRAL AREA [ Tok [ ]See Notes HD SUB-BAGATELLE EQUIP AREA [J [ ]See Notes DD ACS-12 WEST WING FAN RM 5 [J�k k [ ]See Notes PS WEST WING FL 5 NEAR EXIT DOOR 1 !I k [ ]See Notes TS WEST WING FL 5 NEAR STAIR [ Vk [ ]See Notes WF WEST WING FL 5 NEAR STAIR [ /fOk [ ]See Notes TS WEST WING FL 5 NEAR STAIR [ �pk [ ]See Notes PS WEST WING FL 5 NEAR STAIR [/rok [ ]See Notes WF WEST WING FL. 5 NEAR ELEV [ /!fok [ ]See Notes TS WEST WING FL 5 FAR STAIR k [ ]See Notes TTS WEST WING FL 5 FAR STAIR [ k [ ]See Notes TS WEST WING FL 5 FAR STAIR [ �k [ ]See Notes WF WEST WING FL 5 FAR STAIR [ �Qk ( ]See Notes PS WEST WING FL 5 FAR STAIR [ J k [ ]See Notes PS REAR AREA OF BAGATELLE [ qk [ ]See Notes PS WEST WING FAR STAIR EXIT DOOR [. /Jpk [ ]See Notes PS BAGATELLE FNTR DOOR [ ]Ok [ ]See Notes PS SUB-BAGATELT..E EXIT DOOR [ gX ( ]See Notes SD WEST WING FL 6 BY RM 614 [ k [ ]See Notes SD WEST WING FL 6 BY RM 616 1110k [ ]See Notes SD WEST WING FL 6 BY RM 618 1 ( k ( ]See Notes SD WEST WING FL 6 BY RM 620 [ 7 [ ,]See Notes SD WEST WING FL 6 BY RM 627_ [ Ok ( ]See Notes SD WEST WING FL 6 BY RM 624 [ ,' s>k [ ]See Notes SD WEST WING FL 6 BY RM 626 [ k [ ]See Notes SD WEST WING FL 6 BY RM 600 [ '�k [, ]See Notes SD WEST WING FL 6 ELEV LOBBY [ k [ ]See Notes SD WEST WING FL 6 ELEV LOBBY [ Ok [ ]See Notes SD WEST WING FL 7 BY ELM RM [ [ ]See Notes SD WEST WING FL 7 BY MAPLE/ELM RM [ k [ ]See Notes SD WEST WING FL 7 9Y RM 723 [ ]See Notes SD WEST WING FL 7 BY RM 722 [ �JUk [ ]See Notes Contract No. 3219 03/30/2006 16:45 9147691652 FSI PAGE 10 Professional Testing Testing Site: HILTON RYE TOWN SEMI 699 WESTCH'[STER AV FIRE 61121.1 699 WESTCH'.!',STER AVENUE Page 7 RYE BROOK, NY 10573 ID Device Location Results SD WEST WING FL 7 BY RM 707 [ [ ]See Notes SD WEST WING FI, 7 BY RM 718 [ k [ ]See Notes SD WEST WING FL 7 BY RM 716 [ oOk [ ]See Notes SD WEST WING FL 7 BY RM 719 (/ Ok ( ]See Notes SD WEST WING TOP OF FAIR STAIRS [ k [ ]See Notes SA WEST WING FL 8 BY RM 814 [ k [ ]See Notes SD WEST WING FL 8 BY RM $16 [ k [ ]See Notes SD WEST WING FL 8 BY RM 818 [ /]Ok [ ]See Notes SD WEST WING FL 8 BY RM 620 [ /�Ok ( ]See Notes SD WEST WING FL 8 BY RM 822 [. /J' k [ ]See Notes SD WEST WING FL 8 BY RM 829 [ k [ ]See Notes SD WEST WING FL 8 BY RM 825 [ �k C ]See Notes SD WEST WING FL 8 BY RM 800 [ /� [ ]See Notes S❑ WEST WING FL 8 ELEV LOBBY [ k [ ]See Notes SD WEST WING TOP OF ELEV SHAFT [ k [ ]See Notes �Jp SD WEST WING FL 6 TOP OF NEAR STAIR [ �k [ ]See Notes PS WEST WING FL 6 FAR STAIR [ %k [ ]See Notes WF WEST WING FL 6 FAR STAIR [ ] k [ ]See Notes TS WEST WING FL 6 FAR STAIR ( k [ ]See Notes PS WEST WING FL 6 SERVICE LINT{ [ /,9k ( ]See Notes WF WEST WING FL 6 NEAR STAIR ( Ok [ ]See Notes TS WEST WING FL 6 NEAR STAIR [ /j k E ]See Notes PS WEST WING FL 6 NEAR STAIR [ k [ ]See Notes PS WEST WING FL 7 NEAR STAIR [ k [ ]See Notes TS WEST WING FL 7 NEAR STAIR [ /,0k [ ]See Notes TS WEST WING FL 7 FAR STAIR [ //�] k [ ]See Notes WF WEST WING FL 7 FAR STAIR [ k ( )See Notes P$ WEST WING FL 7 FAR STAIR [ /jOk [ ]See Notes PS WEST WING FL B FAR STAIR [ Ik [ ]See Notes WF WEST WING FL 8 FAR STAIR [ k [ ]See Notes TS WEST WING FL 8 FAR STAIR [ qppk [ ]See Notes WF WEST WING FL 8 NEAR STAIR Ok [ ]See Notes TS WEST WING FL 8 NEAR STAIR ( /�Ok [ ]See Notes PS WEST WING FL 8 NEAR STAIR [ /k [ ]See Notes SD ELEV MACH RM BY ENGINEERING [ /�k [ ]See Notes HD MAIN LVL s EL,EV LOBBY MAIN KITCHEN [ /�k [ ]See Notes ED MAIN LVL B CORR LEADING TO ENGINEERING [ /k [ ]See Notes HD MAIN LVL S IN BEVERAGE OFFICE [ Ok [ ]See Notes HD MAIN LVL B LIQUOR STORAGE AREA [/2k [ ]See Notes HD MAIN LVL 3GRAND BALL SERV CORR [ i0k k [ ]See Notes HD MAIN LVL B GRAND BALL SERV CORK [ k [ ]See Notes SD MAIN LVL B AT MIANUS PAY PHONE [ [ ]See Notes HD MAIN LVL B IN MIANUS PAY PHONE (/�k [ ISeE Notes HD MAIN LVT, B IN TUPIL TREE REST. [ k [ ]See Notes SD MAIN LVL B CORR BEHIND TULIP T [ /k [ ]See Notes SD MAIN LVL B CORR BEHIND TULIP T [ k ( ]See Notes SD MAIN LVL B GRAND BALL. ENT/EXIT [ 0k ( ]See Notes HD WOMEN'S RM NEAR GRAND BALL RM [ ]// k [ ]See Notes Contract No. 3219 03/30/2006 16: 45 9147691652 F5I PAGE 11 '. 11 2 C ..t lw1 1 L + N 4 t f F� -0 �t'�MsA1r .i1�N�,;1�711�J1�oSfl�iu�.. 'C f a. Mtn;=,ir.:,. OEM" Professional Testing Testing Site: HILTON RYE TOWN SEMI 699 WESTCH.!::STER AV FIRE 6112=.1 699 WESTCH.;::STER AVENUE Page 8 RYE BROOK, NY 10573 Ip Device Location Results HD MEN'S RM NEAR GRAND BALL RM [ k [ ]See Notes SD BY GRAND BALL PHONES, COAT RM [ k [ ]See Notes SD CORR BETWEEN TULIP AND COAT RM [ k [ ]See Notes SO MAIN LVL C LOBBY CORR BY TULIP [ �k [ ]See Notes SO MAIN LVL C LOBBY BY RECEPTION [ Wok [ ]See Notes SD MAIN LVL C LOBBY BY RECEPTION [/^k [ ]See Notes SO MAIN LVL C LOBBY CORR TO RYE [ /)k [ ]See Notes SO MAIN LVL C LOBBY CORR TO TERRACE 11�. Ok [ ]See Notes SD MAIN LVL C LOBBY CORR TO TERRACE [ , k [ ]See Notes HD MAIN LVL C THE DEN BAR AREA j �k [ ]See Notes HD MAIN LVL C PENFIELDS AREA [ /]Ok [ ]See Notes HD MAIN LVL C PENFIELDS AREA [ /9k [ ]See Notes TS ABOVE CEILING NEAR MIANUS RIVER Z�plc k [ ]See Notes WF MAIN LVL B ABOVE CEILING MIANUS RIV [ [ ]See Notes PS MAIN LVL B EXIT @ GRAND BALL [ / k [ ]See Notes PS MAIN LVL C MAIN LOBBY DOOR ( k [ ]See Notes PS MAIN LVL C DOOR TO TERRACE ( ]Ok [ ]See Notes WE' MAIN LVL C ABOVE CEILING PENFIELDS [/' k [ ]See Notes TS MAIN LVL C ABOVE CEILING PENFIELDS [ . k [ ]See Notes PS MAIN LVL C REAR KITCHEN EXIT ( }Zk [ ]See Notes PS MAIN LVL C PENFIELDS TERR DR I k [ ]See Notes SD MAIN LVL A NEAR SECURITY [ %k [ ]See Notes SD MAIN LVL A CORR NEAR DRY STOR [ /l01c [ ]See Notes HD MAIN LVL A DRY STOR SERV AREA [ �1px [ ]See Notes HD MAIN LVL A DRY STOR SERV AREA [ 1 c [ ]See Notes SD MAIN LVL A CORR NEAR EMP CAFE [ k ( ]See Notes SD MAIN LVL A CORR NEAR TABLE RM [ J k [ ]See Notes SD MAIN LVL A SERV ELEV LOBBY [ k [ ]See Notes SD MAIN LVL A SERV ELEV MACH RM [ /t k [ ]See Notes HD MAIN LVL A LADIES LOCKER RM [ k ( ]See Notes / HD MAIN LVL A EMPLOYEE CAFE [ �Ok [ ]See Notes DD ACS-13 LADIES LOCKER RM [ j ( ]See Notes SD MAIN LVL A SERV CORR TO WEST 6 ( j�k k [ ]See Notes HD MAIN LVL B ELEC SWITCH GEAR RM [�k [ ]See Notes HD MAIN LVL B CARPENTER SHOP/STOR [ �k ( ]See Notes ND MAIN LVL B BOILER RM [ /�k ( ]See Notes HD MAIN LVL S CHILLER/FAN RM NORTH [ C k j ]See Notes HD MAIN LVL B CHILLER/FAN RM CENTER . /�Ok [ ]See Notes HD MAIN LVL B CHILLER/FAN RM SOUTH [ //Ok [ ]See Notes HD MAIN LVL B BY ENG FAN CONTROL PNL [ k [ ]See Notes DD ACR-2 MAIN LEVEL B FAN RM [ 9k [ ]See Notes DD ACR-1 MAIN LEVEL B FAN RM [ k [ ]See Notes DO ACS-1 MAIN LEVEL B FAN RM [ �k [ ]See Notes DO ACS-2 MAIN LVL B FAN RM [��k ( ]See Notes HD GRAND BALL RM ASSEMBLY NORTH [ /]ok [ ]See Notes RD GRAND BALL RM ASSEMBLY CENTER ( /rOk [ ]See Notes HD GRAND BALL RM ASSEMBLY SOUTH j >' k [ ]See Notes HD MAIN LVL B GRAND BALL RM SOUTH 0k ( ]See Notes Contract No. 3219 03/30/2006 16:45 9147691652 FSI PAGE 12 Professional Testing g Westin Site: HILTON RYE TOWN SEMI 699 WESTCB .STER AV FIRE 611,21.1 699 WESTCHI„STER AVENUE Page 9 RYE BROOK, NY 10573 ID Device Location Re S�lts HD MAIN LVL B GRAND BALL RM SOUTH [ ]Qk [ ]See Notes HD MAIN LVL B GRAND BALL RM CENTER WEST [1fqk [ ]See Notes HD MAIN LVL B GRAND BALL RM CENTER EAST [ �k [ ]See Notes HD MAIN LVL B GRAND BALL RM N.EAST [ k [ ]See Notes HD MAIN LVL B GRAND BALL RM N.WEST (�k ( ]See Notes SD MAIN LVL A CORR @ GEN STOR RM [ /1Ok [ ]See Notes SD MAIN LVL A ELEC RM @ CORR TO WEST (/f)k [ ]See Notes DD HV-1 MAIN LVL B FAN RM [ k [ ]See Notes PS MAIN LVL A NEAR SECURITY [ Ok [ )See Notes TS LOADING DOCK DRY SYSTEM [ lk [ ]See Notes PRESSURE SW LOADING DOCK DRY SYS [ Ok [ lSee Notes TS ABOVE CEILING NEAR DRY STOP, AREA [ lf0k [ )See Notes TS ABOVE CEILING CORR TO LOADING DOCK [ /r0k ( ]See Notes WF MAIN LVL A ABV CEILING CORR TO DOCK [ /� k [ ]See Notes TS MAIN LVL A STAIR TO BAN KIT [�J k [ ]See Notes PS MAIN LVL A AT STAIR TO BAN KIT [ ?/k [ ]See Notes PS MAIN LVL A SERV CORR TO WEST [ /JOk ( )See Notes PS MAIN LVL A CORR NEAR FOOD BEF [40k [ ]See Notes TS BY FIRE CYCLE PANEL BY ENG. [ ,j�Q k [ ]See Notes PS MAIN LVL B GRAND BALL RM ASSEMBLY [ l0k [ ]See Notes HD MAIN LVL A LOADING DOCK/COMPACT [lli k [ ]See Notes PS MAIN LVL B KIT REAR CORR EXIT 1Ok k [ ]See Notes HD UPPER BANQ B IN ELIGA BUDD RM [ [ ]See Notes HD UPPER BANQ B IN HALSTEAD II RM ( /�Ok ( ]See Notes HD UPPFR BANQ B HALSTEAD I RM [ /�Ck [ ]See Notes HD UPPER BANQ B IN ODELL RM [ ]See Notes ND UPPER BANQ B IN BARTELL RM [ rpk [ ]See Notes HD UPPER BANQ BI.N BRUNDAGE II RM [ ( ]See Notes HD UPPER BANQ B IN BRUNDAGE I RM [ ',lOk [ ]See Notes HD UPPER BANQ B IN BOTON RM [ /1Ok [ ]See Notes DD HP-1 ACC. OFFICE ABOVE CEILING [ �Ok [ ]See Notes SD MEETING RM CORR BY HALSTEAD II [ )See Notes SD UPPER BANQ B BOARD RM SERVICE [ 'JOk [ ]See Notes SD MEETING RM CORR BY HALSTEAD I [ �Ok [ ]See Notes SD MEETING RM CORR BY BARTELL, RM [ �Ok [ ]See Notes Hp MEN'S REST RM BY BRUNDAGE ROOMS [�,�k [ ]See Notes HD WOMEN'S REST RM BY BRUNDAGE ROOMS [ 'J0k [ ]See Notes SD MEETING RM CORR BY BOTON RM [ -�Ok ( ]See Notes SD UPPER BANQ B CORR TO BOTON RM [ /, p k [ ]See Notes Sp UPPER BANQ B CORR TO BOTON RM [/Ok [ ]See Notes Sp TOP OF STAIR BY MIANUS RIVER [ XOk [ ]See Notes SD LINK CORR TO RYE CTR OF CORR ( --�Ok [ )See Notes SD .LINK CORR TO RYE CTR OF CORR [ j/'Qk [ ]See Notes Sp LINK CORR TO RYE NEAREST RYE [ 1pk ( ]See Notes SD LINK CORR NEAREST STAIR [ k [ ]See Notes Hp UPPER LEVEL B ELEC EQUIP RM 4/4 [ )k [ ]See Notes ( ]See Notes Hp UPPER LEVEL B ELEC EQUIP RM 3/4 [ ! ]See Notes Hp UPPER LEVEL B ELEC EQUIP RM 2/4 [ Contract No. 3219 03/30/2006 16:45 9147691652 FSI PAGE 13 Professional Testing Testing Site: HII.TON RYE TOWN SEMI 699 WESTCH;I:STER AV FIRE 61121.1 699 WESTCH;i:STER AVENUE Page 10 RYE BROOK, NY 10573 LD Device Location Results HD UPPER LEVEL B ELEC EQUIP RM 1/9 [ k [ ]see Notes SD UPPER LEVEL B ELEC EQUIP RM [ ,k [ ]See Notes SD UPPER LEVET., B BY CONTROLLERS OFFICE [ 40k [ ]See Notes HD LAUNDRY RM LEFT FRONT [ /f k [ ]See Notes HD LAUNDRY RM LEFT REAR [ k [ ]See Notes HD LAUNDRY RM RIGHT REAR [/jOk [ ]See Notes HD LAUNDRY RM LEFT FRONT [/fOk [ ]See Notes HD UPPER LVL B HOUSEKEEPING STOR ( /rOk ( ]See Notes HD UPPER LVL B HOUSEKEEPING OFFICE r �pk [ ]See Notes Hp UPPER LVL B HOUSEKEEPING ACCT STOR RM [ k [ ]See Notes HD UPPER LVL B LINEN SUPPLY RM [�J k [ ]See Notes SD UPPER LVL B CORR BY ACCT/LAUNDRY [ Ok [ ]See Notes SD TN ACCT OFFICE COMP RM [ � k [ ]See Notes SD CORR BY ACCT OFFICE ENTR DOOR ( k [ ]See Notes HD UPPER BANQ B MEN'S LOCKER RM [ 2 k [ ]See Notes SD UPPER BANQ A CORR O/^a MEN'S LOCKER [ k [ ]See Notes HD UPPER BANQ B LVL WOMEN'S FM [ ,, O Ok ( ]See Notes HD UPPER BANQ B LVL MENS RM [ /rOk [ l See Notes SD UPPER BANQ B CORR o/S EXEC OFFICE [ ,�Ok [ ]See Notes SD UPPER BANQ B CORR O/S COAT RM [ /fok [ ]See Notes HD UPPER BANQ B COAT RM [5A k [ ]See Notes SD UPPER BANQ B LVL TOP OF STAIR [ /]Gk [ ]See Notes SD ELEV SHAFT UPPER BANQ B LVL [ ]Ok [ ]See Notes SD UPPER BANQ B EXEC OFFICE ]See Notes DD ACS-3 FAN RM #1 UPPER BANQ ]See Notes DD ACR-3 FAN RM 41. UPPER BANQ [ �Ok ( ]See Notes DD ACS-4 FAN RM #1 UPPER BANQ [ ,*,( k [ ]See Notcs DD ACS-5 FAN RM #1 UPPER BANQ [� k [ ]See Notes DD HV-2 FAN RM #1 UPPER BANQ [ Ok [ ]See Notes PS UPPER BANQ B @ ELIJA BUDD RM [ /Qk [ ]See Notes PS UPPER BANQ B BOARD RM SERV [ / Ok [ ]See Notes PS UPPER BANQ B RYE LINK CORR [ /l'-Ok ( ]See Notes WF UPPER BANQ B TOP OF STAIR [/f6k [ ]See Notes TS UPPER BANQ B TOP OF STAIR [JfOk ( ]See Notes PS UPPER BANQ B AT STAIR/ELEV [/�'Qk [ ]See Notes SD CORK NEAR DOOR To WEST D BANQ [ ,�'Ok [ ]See Notes HD WEST BALLRM SECTION D-4 [/ o k [ ]See Notes HD WEST BALLRM SECTION D-5 [,,,rOk [ ]See Notes HD WEST BALLRM SECTION D-6 [/TQk [ 1See Notes HD WEST BALLRM SECTION C-3 [ �Ok [ ]See Notes HD WEST BALLRM SECTION C-2. [ /Ok ( ]See Notes HD WEST BALLRM SECTION C-1 [/ 6k [ ]See Notes HD WEST BALLRM SECTION B-4 ( ,I-Ok [ ]See Notes HO WEST BALLRM SECTION B-5 [ •,fOk [ ]See Notes HD WEST BALLRM SECTION B-6 [ ✓ -k ( ]See Notes HD WEST BALLRM SECTION A-3 [ /j"Ok ( ]See Notes HD WEST BALLRM SECTION A-2 (4�Q'Ik [ ]See Notes HD WEST BALLRM SECTION A-1 [ k ( ]See Notes Contract No. 3219 03/30/2006 16:45 9147691652 FSI PAGE 14 • V vi t .z » Professional Testing Testing Site: HILTON RYE TOWN SEMI 699 WESTCH]i1STER AV FIRE 61121.1 699 WESTCH]i;STER AVENUE Page 11 a - RYE BROOK, NY 10573 ID Device LoCat:i on Results SD CORK NEAR WEST B BALLRM [ . k [ ]See Notes SD CORR NEAR WEST A BALLRM [ 10k [ ]See Notcs SD CORR NEAR WEST A-2 DOOR ( /pk [ ] See Notes SD CORR NEAR A-3 DOOR [ k [ ]See Notes SD CORR NEAR WEST A-3 DOOR [ 40 k [ ]See Notes SD KITCHEN NEAR WEST A-3 DOOR [ 2 k [ ]See Notes HD WEST BANQ KITCHEN NEAR A-3 :�Jp k ( ]See Notes SD TOP OF SHAFT SERV ELEV UPPER ;. �?k [ ]See Notes HD ELEV LOBBY UPPER BANQ LEVEL [ /1 ]c [ ]See Notes HD PORT CHESTER RM UPPER LEVEL [ k [ ]See Notes SD CORR NEAR PORT' CHESTER RM UPPER I/�ok [ ]See Notes HD TOWN OF RYE I RM UPPER LVL ( !1'6k [ ]Sec Notes ]-]D TOWN OF RYE I RM UPPER LVL [ bk [ ]See Notes HD TOWN OF RYE I RM UPPER LVL .IUk [ ]See Notes HD TOWN OF RYE I RM UPPER LVL [ Ak [ ]See Notes SD CORR NEAR TOWN OF RYE II UPPER [ /�O]c [ ]See Notes SD CORR NEAR TOWN OF RYE I UPPER [ �'Ok [ ]See Notes SD CORR NEAR WEST 0-4 UPPER LEVEL [,-fQk ( )See Notes SD CORR NEAR RAMP TO WEST WING [X. [ ]See Notes SD RAMP TO WEST WING UPPER LEVEL [ �k [ ]See Notes SD RAMP TO WEST WING UPPER LEVEL [ Ok [ ]See Notes DD UPPER BANQ A PORT CHESTER RM [ ,;(Ok [ ]See Notes DO UPPER BANQ A TOWN OF RYE II [fJ k [ ]See Notes DD UPPER BANQ A TOWN OF RYE I [ k [ ]See Notes DD ACS-14 FAN RM #1 UPPER BANQ [/�Ok [ ]See Notes DD ACR-15 FAN RM 01 UPPER BANQ [ ,�>k [ ]See Notes DD ACS-15 FAN RM #1 UPPER BANQ [ ,10k [ ]See Notes DD AH-8 FAN RM #1 UPPER BANQ [ JJ/Ok [ ]See Notes PS CORR TO WEST NEAR BANQ RM [ ffOk ( ]See Notes PS WEST BALL RM EXIT LOBBY DOOR [/Ok [ ]See Notes PS UPPER LVL KITCHEN EXIT DOOR [rj� [ ]See Notes pS UPPER LVL KITCHEN EXIT DOOR [ [ ]See Notes WF UPPER LVL STAIR NEAR KITCHEN ]See Notes TS UPPER LVL STAIR NEAR KITCHEN [ /�k ( ]See Notes TS UPPER. LVL STAIR NEAR KITCHEN [ �k [ ]See Notes WF UPPER LVL STAIR NEAR KITCHEN j ]///!!] k [ ]See Notes WF FAN RM #1 UPPER LVL [ k [ ]See Notes TS FAN RM #1 UPPER LEVEL [ k [ )See Notes PS UPPER LEVEL EXIT DOOR NEAR KITCHEN [ k [ )See Notes PS UPPER LEVEL NEAR RAMP TO WEST ( ]ok [ ]See Notes Contract No- 3219 03/30/2006 16:45 9147691652 FSI PAGE 15 Professional Testing Testing Site: HILTON RYE TOWN SEMI r.. 699 WESTCK:I:STER AV FIRE 61121.1 699 WESTCH ';STER AVENUE Page 12 RYE BROOK, NY 10573 ID Device Location Results Panel Tested: y�K [] See notes Batteries Tested: [V OK [I See notes [] N/A Remote Signal Tested: VOK [] See note [1 N/A Changes to this report from ,last �testing? [ o [] Yes, see attached Technician: ,N �o �' Date Tested: -n lot. Notes: Contract No. 37.19