January 26,2021
1100 King Street Associates
C/O George Comfort& Sons, Inc.
4 International Drive
Rye Brook,NY 10573
Attn: Larry Christ
Re: 1100 King Street,Annual Elevator Inspections-Rye Brook New York
Dear Sir:
On January 22 & 23 2021 I witnessed the code required annual no load hydraulic pressure and safety
tests on twelve(12)passenger elevators located at the above referenced address as performed by your
elevator maintenance company Liberty Elevator Corp.
The elevators were tested to ensure compliance with testing procedures required by ASME A17.1 Safety
Code for Elevators and Escalators as referenced by the NYS Building Code, Chapter30
The following violations were revealed that require correction to comply with code:
Building#I
Elevators# 1&2
1. When cars are on fire recall Phase I and return to lobby the fire buzzers must turn off.
2. Fire recall lights must remain on during Phase I and II operation.
Elevator#2
1. Replace 2 missing car platen plate bolts
Building#2
Elevator# 1
Fire recall lights must remain on during Phase I and I1 operation and buzzers must turn off.
Elevator#2
1. Car does not recall on Phase I
2. Control valve relief is set at 600psi; it must be set to approximately 450 Psi
3. Fire recall lights must remain on during Phase I and II operation.
Building#3
Elevators#1 &2
1. When cars on fire recall phase I and return to lobby the fire buzzers must turn off and fire lights must
stay on.
Elevator#2
1. In-car emergency Phone does not work.
2. Replace broken emergency light lens.
"A aul
Certified C-875 <IVAESA
S `W Certified Elevator Inspections, Inc. `�e199375
7-11 Legion Drive, Suite 103. Valhalla. NY 10595 • Phone: 914 428-3419 Fax: 914 428-5501 • johnceict optonline.net
Pe.2
1100 King Street Associates
C/O George Comfort& Sons, Inc.
4 International Drive
Building#4
Elevators# 1&2
1. When cars are on fire recall and return to lobby the fire buzzers must turn off and lights stay on.
Elevators#1
1. In—car emergency phone does not work.
Building#S
Elevators# 1 &2
1. In—car emergency lights and alarm do not work.
Building#6
Elevators# 1 & 2
1. When cars are on fire recall and return to lobby,the fire buzzers must turn off, lights must remain on.
Elevator#2
In—car emergency lights and alarm do not work.
The violations listed must be corrected in a timely manner as required by the Village of Rye Brook
Building Inspector.
Elevators are deemed safe to operate, but compliance is mandatory!
Please notify this office when all violations have been complied with so that a reinspection can be made
and we can provide you with a compliance letter.
If you have any questions regarding this report,please feel free to contact my office.
Yours truly,
l r-
ohn G. Boc inis
Certified Elevator Inspections
NAESA QEI Cert. #C-875
Certified Since 1993
C.c.Michael J. Izzo Village of Rye Brook, Liberty Elevator Corp.