HomeMy WebLinkAboutElevator Inspection 2.2020 Arl WA Cenified C-875 Certified C-875 Sincc 1993 Certified Elevator Inspections, Inc. Since 1993 7-11 Legion Drive, Suite 103. Valhalla, NY 10595 • Phone: 914 428-5419 Fax: 914 428-3501 • johncei@optonline.net February 21, 2020 D E�E O V LS 1100 King Street Associates C/O George Comfort & Sons, Inc. MAR -3 2020 4 International Drive Rye Brook,NY 10573 VILLAGE OF RYE BROOK Attn: Larry Christ BUILDING DEPARTMEE Re: 1100 King Street, Annual Elevator Inspections-Rye Brook New York Dear Sir: On February 19,20,2020 I witnessed the code required annual no load hydraulic pressure and safety tests on twelve(12)passenger elevators located at the above referenced address as performed by your elevator maintenance company Liberty Elevator Corp. The elevators were tested to show compliance with testing procedures required by ASME A17.1 Safety Code for Elevators and Escalators as referenced by the International Building Code. At the time of the inspections, the following violations were revealed that require correction to comply with code: Building # 1 Elevators# 1& 2 1. Replace two missing piston Platen plate bolts,requires four. 2. Emergency lighting and alarm does not work. Elevator#2 1. Remove excessive oil from catch pan. 2. Does not recall on Phase 1 3.Emergency lighting and alarm does not work. Building # 2 Elevators# 1 &2 1. In-car emergency lights and alarms do not work. 2. Provide and install an engraved plaque on each car button station stating Elevator number. Building # 3 Elevators# 1 &2 1. Remove excessive oil from catch pans. arl Aul A V%A Certified C-875 Certified C-875 Since1993 Certified Elevator Inspections, Inc. Sincel993 7-11 Legion Drive, Suite 103, Valhalla, W 10595 • Phone: 914 428-3419 Fax: 914 428-3501 • johncei@optonline.net Pa.2 1100 King Street Building # 4 Elevator#1&2 1. In—car emergency phones do not work. Building # S Elevators#1 &2 1. In—car emergency phones do not work. 2. In-car alarm bell does not work when stop switch is activated. 3. Provide and install an engraved plaque on each car button station stating Elevator number. Building # 6 Elevators# 1 &2 1. Test Satisfactory All Elevators The type of elevator controls installed in these buildings predates the use of a call cancel button when the elevators are on phase II operation. The recent installation of new car button fixtures in all the elevators, Incorporate a call cancel button. The call cancel button in each elevator must be removed and blanked off as to not confuse the local fire fighters during an emergency. The violations listed must be corrected in a timely manner as required by the Village of Rye Brook Building Inspector. Please notify this office when all violations have been complied with so that a reinspection can be made and provide you with a compliance letter. If you have any questions regarding this report,please feel free to contact my office. Yours truly, ?J-o n G. Bochinis Certified Elevator Inspections NA ESA QE1 Cert. #C-875 Certified Since 1993 C.c.Michael J. Izzo Village of Rye Brook Liberty Elevator Corp.