Loading...
HomeMy WebLinkAbout2015-12-07 Sun Homes E.S.T.F. Memo BUILDING DEPARTMENT VILLAGE OF RYE BROOK 938 KING STREET RYE BROOK,NY 10573 (914)939-0668 Phone (914)939-5801 Fax mizzo yebrook.org Memorandum To: Gerhard M. Schwalbe, P.E., Divney, Tung& Schwalbe From: Michael J. Izzo, Building & Fire Inspector qA�- CC: Planning Board Emergency Services Task Force (ESTF) Date: December 7, 2015 Re: ESTF review of the Fire Protection Plan for the proposed Sun Homes Residential Development at the Reckson Office Campus. The following review is based on materials submitted by Divney,Tung & Schwalbe, Intelligent Land Use, on behalf of the applicant, Sun Homes, for the proposed residential development at the Reckson Office Campus located at 1100 King Street. Reviewed materials include; • Cover Letter dated,November 24, 2015, signed by Gerhard M Schwalbe, P.E. • Sun Homes Fire Protection Plan, sheet F-1, dated 11118115, prepared by Divney, Tung & Schwalbe. The plan is not sealed. 1. FCNYS 503.2.1. The minimum required unobstructed width of a fire apparatus access road is twenty (20) feet. The Fire Protection Plan includes a"part plan'in the upper right hand corner indicating the existing brick pillars to remain in place at the proposed emergency service access road at King Street. My field measurement confirmed the distance between the existing pillars is only 17.65 feet. Therefore the applicant must reconfigure or remove the existing brick pillars to provide a minimum unobstructed width of twenty (20) feet. 2. The applicant shall provide crash bollards, installed as per FCNYS §312, spaced at least twenty(20) feet apart with chains across the emergency access road at the following locations; a. At the King Street entrance. b. At the transition from the emergency access road to the common parking Iot. c. At the transition from the common parking lot to the interior emergency access road. d. At the intersection of the interior emergency access road and the Sun Homes Development private street. 3. The applicant shall provide approved signs identifying the emergency access road reading;NO PARKING - EMERGENCY VEHICLES ONLY, at the four(4) emergency access road intersections described in items 2. a, b, c, & d, above. 4. The applicant shall provide proposed topographic & construction drawings for the emergency access road showing compliance with FCNYS 503.2, 503.2.1, 503.2.3, and 503.2.7, to be reviewed and approved by the Building Department. 5. The applicant shall make provisions for perpetual maintenance of the emergency access road, including that portion of the existing parking lot now dedicated to such emergency access in good repair, and shall maintain the entire thoroughfare free from leaves, branches, limbs, accumulated ice and snow& other debris at all times. The ESTF respectfully requests that language pertaining to such perpetual maintenance of the emergency access road& thoroughfare be included in the Final Approval Resolution. 6. The applicant must relocate two (2) fire hydrants and install one (1) additional fire hydrant as per the attached ESTF Fire Hydrant Re-location Plan, dated 1217115 as initialed by me. 7. The applicant must provide the fire flow information for review& approval by the Village. S. All interior roads are to be dedicated Fire Lanes in conformance with Village Code §240-22.A, and shall be indicated with signs posted in accordance with Village Code §240-22.C.(b), and §240-22.D. 9. Village Code §240-22.B.(1)requires emergency access in the immediate vicinity of the proposed Clubhouse. The applicant is proposing public parking in this area. Therefore the applicant must reconfigure the proposed clubhouse/clubhouse parking so as to comply with this section of code. 10. The applicant must submit a street naming/numbering plan based on the attached recommended ESTF Road Plan, dated 12/7115 as initialed by me. International Drive shall be used as the name of the main entrance roadway, and a code compliant street sign shall be provided for same at the intersection of International Drive & King Street. 11. The applicant must provide dimensioned, proposed rear building elevations for those buildings which back up on interior or perimeter storm water basins. The applicant must also show all proposed interior storm water retention basins (rain gardens) and existing and proposed perimeter storm water retention basins and any proposed fencing of same at these building locations, showing adequate access and setbacks for rear yard Fire Department ground ladder operations. 12. The applicant must show& provide details for the relocated trash compacter and maintenance yard, which is currently located in the area of the proposed interior emergency access road and FAH units. 2 z i 0 o0 g, 111s 0-4 tj 'a D I ...... .......... C> n1111ILLEILULLIn P11111111111111111 ITM u 1111111111 Ill 1114 'Ut"I m OHHHHHHHHHHD UIIIII THHHHHH L LLJ 'uj�.0 LJiJ-1 UILWIAlIII i kg ritl r ----------- ----L-L—--—-- - V) 11 Il nl Is li �rrsea Oa ii;L't 'Ah OR qz i�5 "' �, L,C y ii; H ,1 21 o 4 LLLLLLLUJI) X1, —)W\u m w to, kk fA